ABB SACE PR010/T Manual De Instrucciones página 11

Tabla de contenido

Publicidad

A continuación puede verse un ejemplo de informe de prueba:
TEST REPORT WITH SACE PR010/T
Version SW: 3.2
********************************
Date:
Hour:
Operator:
Relay S.Nr.:
Relay type:
Relay version:
CB type:
CT rated current:
Neutral:
********************************
Protection:
Threshold [In]:
Curve [s]:
Curve type:
Tested phase(s):
Fault current [In]:
Expected time [s]:
Measured time [s]:
Test result:
Protection:
Threshold [In]:
Curve [s]:
Curve type:
Tested phase(s):
Fault current [In]:
Expected time [s]:
Measured time [s]:
Test result:
Protection:
Threshold [In]:
Curve [s]:
Curve type:
Tested phase(s):
Fault current [In]:
Expected time [s]:
Measured time [s]:
Test result:
Protection:
Threshold [In]:
Curve [s]:
Curve type:
Tested phase(s):
Fault current [In]:
Expected time [s]:
Measured time [s]:
Test result:
ABB SACE
03/05/00
13:55
Belometti
M0047C03B
PR112
LSIG
E1B800
250 A
50%
L
0.400
3.00
t=k/i^2
L1
2.40
0.750
0.758
OK
S
0.800
0.35
t=k/i^2
L1
1.60
13.668
11.984
OK
I
4.000
inst
t=k
L1
8.00
0.060
0.016
OK
G
0.400
0.10
t=k/i^2
—-
1.00
0.320
0.314
OK
SACE PR010/T
RH0025005
L2551
19
9/19