Ratings
Heavy duty non-fusible safety switches
1
Non-fusible safety switch
AMPS
General purpose current rating
Max. horse power rating
Max. motor FLA current
Short circuit rating
Ground bus
Ground bus catalog number
Temperature rating
Auxiliary contacts, optional
Suitable auxiliary contacts
Nema ratings, AC
AC rated voltage
AC rated thermal current
AC maximum volt-ampere making
AC maximum volt-amperage breaking
Nema ratings, DC
DC rated voltage
DC rated thermal current
DC maximum make-break
1/6 Ratings | Instruction Bulletin EOHU361/2/3JK/RK/S/SS, 1SCC340036M1401 / A
Three phase
240 V
480 V
600 V
Three phase
240 V
480 V
600 V
Class R, J or T fuses
480 V
600 V
Function
EOHU361_
A
30
A
30
HP
10
HP
20
HP
30
A
28
A
27
A
32
kA
200
kA
200
OZXG1
°F
167
°C
75
1NO
OA1G10
1NC
OA3G01
AC600
VAC
600
A
10
VA
7200
VA
720
R300
VDC
300
A
1
VA
28
EOHU362_
EOHU363_
60
100
60
100
20
40
50
75
60
100
54
104
65
96
62
99
200
200
200
200
OZXG1
OZXG1
167
167
75
75
OA1G10
OA1G10
OA3G01
OA3G01
AC600
AC600
600
600
10
10
7200
7200
720
720
R300
R300
300
300
1
1
28
28