SKID TANK INSTALLATION
700F2170 ADAPTER
DIRECT MOUNTING INSTALLATION
14.12
358.6 mm
5.88
149.4 mm
10.00
254 mm
31 IN.
787.4 mm
MAXIMUM LIFT
Gasoline - 10' (3 m)
Diesel
- 15' (4.5 m)
-Models FR700:
12" (305 mm) Front to back (side)
-Models FR701:
14" (356 mm) Front to back (side)
JUNCTION
BOX
PUMP
SKID TANK
5.25
133.4 mm
11.25
285.8 mm
PUMP
700F2170 ADAPTER
2" STD. PIPE COUPLING
1" SUCTION PIPE
2" PIPE
GROUND LINE
TANK LINE
FLUID
LEVEL
END OF PIPE TO BE
WITHIN 3 IN. (76.2 mm)
OF TANK BOTTOM
RECOMMENDED ISLAND INSTALLATION
32 1/2"
1 7/8"
1/2" BOLTS
1 7/8"
7 25/32"
PUMP
FRONT
7 25/32"
LAYOUT FOR
BASE ANCHOR BOLTS

WIRE DIAGRAM

BLACK
AC
BROWN
AUX.*
WHITE
NEUTRAL
GREEN
GROUND
WARNING:
*
AUX. WIRE IS LIVE WIRE!
The AUX. lead wire is insulated and enclosed when shipped.
Do not connect this wire without first verifying the 'ON' line
voltage of the wire for compatibility to the equipment to be
installed. Maximum amperage on wire is 1 ampere. The wire
must be insulated and enclosed in the junction box if not used.
2
PUMP
600F2130 PEDESTAL PIPE
1" SUCTION PIPE
ELECTRICAL CONDUIT
700F3060 PUMP BASE
CONCRETE ISLAND
36" SQUARE
TANK LINE
END OF 1" OR LARGER SUCTION
PIPE MUST BE AT LEAST 3" OFF
BOTTOM OF TANK
ELECTRICAL
CONDUIT
4" DIA.
CLEARANCE HOLE
MOTOR