FPC-500-2 | FPC-500-4 | FPC-500-8
NOTICE!
The maximum current of the zones is 100 mA ±5 mA.
Each zone must be completed with a terminal element.
NOTICE!
Per DIN VDE 0833-2, zones may only contain manual call points
or automatic detectors. Mixed operation is not allowed in a
zone.
Observe local regulations for the maximum number of detectors
in a zone.
Aux power
EN54-13
Notification appliances
NOTICE!
Each notification appliance output provides connected
notification appliances with a maximum current of 500 mA at
24 VDC.
Bosch Sicherheitssysteme
Non-EN54-13
EOL
b+
a-
4W
+
-
3,9kΩ
b+
a-
4W
+
-
FLM-320-EOL4W
- - + +