Dimensions; Installation Of The Unit; Connections; Hydraulic Connections - PSA Zodiac Red Line Manual De Instalación Y De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 41

2.2 Dimensions

Model
Red Line 3
Red Line 6
Red Line 9
Red Line 12

3. INSTALLATION OF THE UNIT

The appliance shall be installed in a technical facility close to the filter of the pool. It shall be horizontally fixed onto
the wall, by means of 2 brackets (not provided), at the lowest level of the hydraulic circuit in order to make sure it is
always full of water (Risk of dry fire otherwise)

4. CONNECTIONS

4.1 Hydraulic connections

The electric heater shall be connected in line to the return circuit downstream the filtration process, with a minimum
flow rate of 5 m³/h up to 30 m³/h. If the flow rate is over 30 m³/h, the appliance shall be installed on a by-pass.
The appliance is delivered with 2 PVC union-socket Ø 63 fittings and 2 reductions 63/50.
Caution: make sure the appliance is installed the way it always contains water, even when the filtration is not running.
Risk of dry fire otherwise.
Caution: The appliance shall be installed upstream any disinfection's process.
A (mm)
538
538
638
638
Minimum
Minimum
15 à 20 cm
15 à 20 cm
3
B (mm)
452
452
552
552
1 –Pump
2 – Filter
3 – Disinfection's process
GB