12 | Installation
Canadian Wiring - auxiliary terminal block and connections
Fitting the auxiliary terminal block (see diagram below).
Fig. 7
For Canada only (Not for U.S.A.)
▶ Connect the red wires from the left hand terminal of the
new block to the L1 terminals in the unit.
▶ Connect the blue wires from the right hand terminal of the
new block to the L2 terminals in the unit.
▶ Push and click the auxiliary terminal block onto the
louvered rail in the backplate.
Connecting the supply cable - Canada only - not for the USA.
The WH36 requires a 220/240V AC single
phase supply protected by a double pole
circuit breaker rated at 180 amps.
•
The power cable size and the installation must be in
accordance with the Canadian Electrical Code, C22.1-02.
•
The incoming hole diameter on auxiliary terminal block can
accept up to 1/0 AWG size cables.
•
The cable entry is via the 1 ¼ inch cable entry hole on the
bottom right hand edge of the back plate.
•
Strip back the insulation on the power wires about ½ inch.
Connect the ungrounded conductors to the terminals "L1"
and "L2" on the auxiliary terminal block.
6 720 647 022 (2014/06)
•
Any insulation on the ground wire should be stripped back
about ¾ inch. The ground lead must be connected to the
pillar terminal marked "GR."
•
Make sure the terminal block screws are tightened
securely. Loose connections can cause wires to heat up.
•
Make sure that the ground wire is wrapped around its
terminal stud and into the saddle washer. The nut should be
tightened securely.
•
Attach the front cover and tighten the retaining screws.
Tronic 5000C