tau K570M Guía Para La Instalación página 12

Ocultar thumbs Ver también para K570M:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

1 - 2 - 3
POWER input 230 Vac 50Hz (115 Vac 60 Hz). 1= PHASE 2= EARTH 3= NEUTRAL
4 - 5
FLASHING LIGHT output 230 Vac 50 W max. The signal is already modulated for direct
use. Flashing frequency increases slightly during closing
6 - 7 - 8
MOTOR output single-phase 230 Vac common= 6; closing= 7; opening= 8; connect the
capacitor between terminals 7 and 8.
9 - 12
OPEN/CLOSE pushbutton input (Normally Open contact);
10 - 12
PEDESTRIAN pushbutton input (Normally Open contact);
11 - 12
STOP pushbutton input (Normally Closed contact);
13 - 15
PHOTOCELL OR SAFETY DEVICES input (Normally Closed contact); They stop the
gate during closing and totally reopen it; they temporarily stop the gate during opening in
order to allow the obstacle to be removed (if dip switch n° 3 set to ON), (13= Common).
N.B.
The photocell transmitter must always be supplied by terminals no. 22 and no. 24,
since the safety system test (phototest) is carried out on it. Without this connection,
the control unit does not work. To override the testing of the safety system, or when
the photocells are not used, set dip-switch no. 7 to OFF.
13 - 14
FIXED SAFETY EDGE input (Normally Closed contact);
Works only when the gate is opening; temporarily stops the gate and partially closes it by
about 20 cm in order to allow the obstacle to be removed. (13=Common).
16 - 17
433,92 MHz built-in RX aerial input; 16= EARTH 17= SIGNAL
18 - 19
2nd RADIO CHANNEL output used for opening/closing another gate or controlling
garden illumination.
20 - 21
GATE OPEN LED output 24 Vac - max. 3 W; the LED fl ashes slowly during opening,
remains on when the gate is open and fl ashes rapidly during closing.
22 - 24
24 Vac 10 W POWER output for PHOTOCELL TX max. no. 1 photocell transmitter.
23 - 24
24 Vac 10 W POWER output for PHOTOCELL RX, EXTERNAL RECEIVERS, etc.
connect a max. of 3 pair of photocells;
25 - 26
OPEN LIMIT SWITCH input (Normally Closed contact); 25= Common.
25 - 27
CLOSE LIMIT SWITCH input (Normally Closed contact); 25= Common.
TRIMMER
T.C.A.
Automatic closing time adjustment from 5 to 120 seconds.
RALL.
Deceleration time adjustment: from 0 to 15 sec. before the limit switch;
Note: the automation must perform a complete opening and closing manoeuvre
before setting the deceleration.
12
TERMINAL BOARD CONNECTIONS
K570M
LOGIC ADJUSTMENTS
TAU
Srl

Publicidad

Tabla de contenido
loading

Tabla de contenido