Tone
Tone Type
1.
970Hz (BS5839-1:2002)
2.
800Hz/970Hz @ 2Hz (BS5839-1:2002)
3.
800Hz – 970Hz @ 1Hz (BS5839-1:2002)
4.
970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)
5.
970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)
6.
554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )
7.
500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) Dutch Slow Whoop
8.
420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)
9.
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)
10.
550Hz/440Hz @ 0.5Hz
11.
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)
12.
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)
13.
1200Hz – 500Hz @ 1Hz (DIN 33 404)
14.
400Hz
15.
550Hz, 0.7s/1000Hz, 0.33s
16.
1500Hz – 2700Hz @ 3Hz (Vandal Alarm)
17.
Simulated Bell
18.
2130Hz
19.
660Hz
20.
660Hz 1.8s ON/1.8s OFF
21.
660Hz 0.15s ON/0.15s OFF
22.
510Hz, 0.25s/ 610Hz, 0.25s
23.
800/1000Hz 0.5s each (1Hz)
24.
250Hz – 1200Hz @ 12Hz
25.
500Hz – 1200Hz @ 0.33Hz.
26.
2400Hz – 2900Hz @ 9Hz
27.
2400Hz – 2900Hz @ 3Hz
28.
800Hz – 970Hz @ 100Hz
29.
800Hz – 970Hz @ 9Hz
30.
800Hz – 970Hz @ 3Hz
31.
800Hz, 0.25s ON/1s OFF
32.
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
33.
340Hz
34.
1000Hz
35.
1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)
36.
660Hz 6.5s ON/13s OFF
37.
1000Hz/2000Hz, 1s each
38.
720Hz, 0.7s ON/0.3s OFF
39.
970Hz, 0.25s ON/OFF
40.
2800Hz, 1s ON/OFF
41.
2800Hz 0.25s ON/OFF
42.
2400/2900 @ 2Hz
43.
Chime, 554Hz/440Hz Single shot 'ding dong'
44.
Chime, 554Hz/440Hz Repeating 'ding dong'
45.
Chime, 970Hz/800Hz Single shot 'ding dong'
46.
Chime, 970Hz/800Hz Repeating 'ding dong'
47.
Hooter, Repeating
48.
Gentle alarm - Tone 2, rises slowly to full volume over 30s
49.
Time-Out Alarm – As Tone 2, cuts off after 10 mins
50.
Time-Out Alarm – As Tone 2, cuts off after 2 mins
51.
750Hz 0.33s ON/0.51s OFF
52.
750Hz 0.51s ON/0.33s OFF
53.
550Hz, 0.33s/1000Hz, 0.7s
54.
600Hz – 900Hz/ 0.9s
55.
660Hz – 680Hz/ 0.9s
56.
670Hz – 725Hz/ 0.9s
57.
920Hz – 750Hz/ 0.9s
58.
700Hz - 900Hz, 0.3s/0.6s OFF
59.
900Hz - 760Hz, 0.6s/0.3s OFF
60.
750Hz
61.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
62.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
63.
Power Only – Use with Stage 3 control for manual/intermittent horn triggering
64.
Reserved for future use
Texecom Ltd (Incorporating Klaxon Signals)
St Crispin Way, Haslingden, BB4 4PW, UK
+44 1706 233879
Installation Instructions
NL
FR
Tone Description / Application
+44 1706 223450
Nexus 105 AC Sounder & Sounder-Beacon
ES
PT
sales@klaxonsignals.com www.klaxonsignals.com
@
IT
PL
Dip Switch
(S1/S2)
O-O-O-O-O-O
O-O-O-O-O-I
O-O-O-O-I-O
O- O-O- O-I- I
O-O-O-I-O-O
O- O-O- I-O- I
O-O -O-I- I-O
O - O - O - I - I - I
O-O-I-O-O-O
O -O-I- O-O -I
O-O- I-O- I- O
O - O - I - O - I - I
O -O-I- I-O- O
O - O - I - I - O - I
O - O - I - I - I - O
O - O - I - I - I - I
O-I-O-O-O-O
O-I- O-O- O-I
O- I-O- O-I -O
O - I - O - O - I - I
O -I- O-I - O-O
O - I - O - I - O - I
O - I - O - I - I - O
O - I - O - I - I - I
O-I- I- O-O- O
O - I - I - O - O - I
O - I - I - O - I - O
O - I - I - O - I - I
O - I - I - I - O - O
O - I - I - I - O - I
O - I - I - I - I - O
O - I - I - I - I - I
I-O-O-O-O-O
I-O- O-O- O-I
I- O-O- O-I - O
I - O - O - O - I - I
I- O-O- I -O- O
I - O - O - I - O - I
I - O - O - I - I - O
I - O - O - I - I - I
I- O-I-O -O-O
I - O - I - O - O - I
I - O - I - O - I - O
I - O - I - O - I - I
I- O - I - I - O - O
I - O - I - I - O - I
I - O - I - I - I - O
I - O - I - I - I - I
I-I - O-O- O-O
I - I - O - O - O - I
I - I - O - O - I - O
I - I - O - O - I - I
I - I - O - I - O - O
I - I - O - I - O - I
I - I - O - I - I - O
I - I - O - I - I - I
I - I - I - O - O - O
I - I - I - O - O - I
I - I - I - O - I - O
I - I - I - O - I - I
I - I - I - I - O - O
I - I - I - I - O - I
I - I - I - I - I - O
I - I - I - I - I - I
Issue 5.0 (August 2010) 18-186457-5
Copyright © Texecom Ltd
SE
DK
Peak Sound
Level (dBA@1m)
105
106
105
106
106
106
109
104
107
106
108
108
106
103
106
112
106
110
105
104
104
105
106
103
109
111
111
106
106
106
106
109
103
105
105
104
107
107
106
108
108
113
102
102
103
104
104
106
106
106
106
106
107
108
106
107
108
105
108
107

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Klaxon Nexus 105 AC

  • Página 1 Nexus 105 AC Sounder & Sounder-Beacon Installation Instructions Tone Tone Type Tone Description / Application Dip Switch Peak Sound (S1/S2) Level (dBA@1m) 970Hz (BS5839-1:2002) O-O-O-O-O-O 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O-O-O-O-I 800Hz – 970Hz @ 1Hz (BS5839-1:2002) O-O-O-O-I-O 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) O- O-O- O-I- I 970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)
  • Página 2: Installation Instructions

    Nexus 105 AC Sounder & Sounder-Beacon Installation Instructions Installation Manual Installation Controls a. Tone Selection IMPORTANT The alarm tones are set using 6-way dipswitches S1. The required a. The unit should be fitted with a fused spur incorporating an all pole settings are shown in the table overleaf.
  • Página 3: Spécifications Techniques

    Stoßfestes Polykarbonat/ABS Niveau de protection poussière/eau IP66 avec presses étoupes IP-Klasse IP66 appropriées Synchronisierung Automatisch mit Klaxon Nexus- Synchronisation Automatique avec les sondeurs und Sonos-Alarmgebern Klaxon Nexus et Sonos *je nach gewähltem Ton. *variable selon la tonalité sélectionnée La directive européenne " Déchets d'Equipements Electriques et Electroniques "...
  • Página 4: Montage-Instructies

    Montageinstructies Instrucciones de Instalación Instalación Installatie a. La unidad debería ajustarse con un cilindro recto soplado que incorpora a. Het apparaat moet voorzien zijn van een aansluiting met aarding die un dispositivo de desconexión de todos los polos y proporciona una voorzien is van een ontkoppelingapparaat voor alle polen en met een separación de contacto de 3 mm en todos los polos.
  • Página 5: Manual De Instalação

    Manual de Instalação Istruzioni di installazione Instalação Installazione a. A unidade deve ser instalada com uma derivação com fusível incorporando a. L'unità deve essere installata con un supporto di sostegno con fusibili um dispositivo de desligamento de todos os pólos que proporciona contenente un dispositivo di disconnessione di tutti i poli che fornisce 3mm de separação entre os contactos de todos os pólos.
  • Página 6: Instrukcja Montażu

    Instrukcja montażu Installationsmanual Installation Instalacja a. Urządzenie powinno posiadać zabezpieczony wyłącznik umożliwiający a. Enheten ska förses med ett säkrat uttag med en frånslutningsanordning odłączenie wszystkich biegunów tak, aby odległość między stykami för alla poler som ger ett kontaktavstånd på 3 mm för polerna. wynosiła 3 mm.
  • Página 7: Teknisk Specifikation

    Installationsanvisninge Installation a. Apparatet skal udstyres med en afgreningsledning med sikring og frakoblingsmulighed for alle poler, der skal give en kontaktafstand på 3 mm ved alle poler. Sørg for at mærkeeffekt for sikring, kabelstørrelse samt type pakdåse er tilstrækkelig til den samlede belastning på lydalarmens kredsløb.

Tabla de contenido