Configuration
Configuration Dip Switch Settings
DIP SWITCH GROUP A
BATTERY TYPE / VOLTAGE POINT
Using a small tool, set the 4 "Battery Type / Voltage Point" Configuration DIP Switches, Group
A (located on the front panel of your APS; see Diagram 1, p. 36) to select battery type and set
the voltage range outside of which your APS will switch to battery power.
• Select Battery Type
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be
degraded or damaged over an extended period of time. See "Battery Selection," page 8 for more information.
Battery Type
Gel Cell (Sealed) Battery
Wet Cell (Vented) Battery
• Select High AC Voltage Switch To
Battery Point
Voltage
264V
259V
• Select Low AC Voltage Switch To
Battery Point
Voltage
201V
182V
163V
144V
Most loads will perform adequately when your APS's High AC
Voltage Point DIP Switch #2 is set to 259V and its Low AC Voltage
Point DIP Switches #3 and #4 are set to 182V. However, if your APS
frequently switches to battery power due to momentary high/low line
voltage swings that would have little effect on equipment operation,
you may wish to adjust these settings. By raising the High AC
Voltage Switch to Battery point and/or lowering the Low AC Voltage
Switch to Battery Point, you may reduce the number of times your
APS switches to battery due to voltage swings.
* Factory default settings
1/3/02
(All models)
(DIP Switch #1, Group A)
Switch Position
Up
Down*
(DIP Switch #2, Group A)
Switch Position
Up
Down*
(DIP Switches #4, Group A & #3, Group A)
Switch Postion
#4 Up & #3 Up
#4 Up & #3 Down
#4 Down & #3 Up
#4 Down & #3 Down*
5
5:18 PM
Page 5
4 3 2 1
4 3 2 1
4 3 2 1
4 3 2 1
4 3 2 1
4 3 2 1
Gel Cell
Wet Cell*
264V
259V*
201V
182V
163V
144V*