Safe Use Instructions — ControlWave Micro
Declaration of Conformity
Hereby, Remote Automation Solutions declares that
the ControlWave Micro product is in compliance with
the essential requirements and other relevant
provisions of European Directives 2004/108/EC (EMC)
and 94/9/EC (ATEX).
CAUTION
When installing units in a hazardous area,
make sure all installation components
selected are labeled for use in such areas.
Installation and maintenance must be
performed only when the area is known to be
non-hazardous. Installation in a hazardous
area could result in personal injury or property
damage.
Always turn off the power to the ControlWave
Micro before you attempt any type of wiring.
Wiring of powered equipment could result in
personal injury or property damage.
To avoid circuit damage when working inside
the unit, use appropriate electrostatic
discharge precautions, such as wearing a
grounded wrist strap.
Do not open enclosure unless area is known to be non-
hazardous.
SPECIFICATIONS: ControlWave Micro
POWER
External Power Input: 10.7 to 30 V dc (+12 V dc) or
21.7 to 30 V dc (+24 V dc), depending on configuration
of jumpers switches, reverse polarity protection.
Input: 10.7 to 30 V dc, 3A max, 36 watts max.
Reference ratings for each device are:
396560-01-6: 2 mA @ 3.3 V dc
396560-02-4: 2 mA @ 3.3 V dc
396563-16-3: 240 mA @ 3.3 V dc
396581-06-4: 145 mA @ 3.3 V dc
396657-02-8: 2A @ 24 V dc
4A @ 12 V dc
396686-01-0: 96 mA @ 120 V ac
40 mA@ 3.3 V dc
396897-02-9: 46 mA @ 3.3 V dc
24.3 mA @ Vext (11-30 V dc)
ENVIRONMENTAL
Operating Ambient Temperature: —40 to +70C.
Storage Temperature: —40 to +85C.
Operating Humidity: 15 to 95%, non-condensing.
WEIGHT
0.36 kg (4-slot base unit or 4-slot expansion unit).
APPROVALS
ATEX/IECEx
Evaluated per the following standards:
EN 60079-0 (2012)
EN 60079-15 (2010)
th
IEC 60079-0 (6
Ed)
th
IEC 60079-15 (4
Ed)
DEMKO 13 ATEX 1203X
Product Markings for Hazardous Locations:
Ex nA IIC T4 Gc, —40°C T
II 3 G.
The following tools are required for installation,
maintenance, and troubleshooting:
Personal computer running Microsoft
XP (with Service Pack 3) or Windows 7.
ControlWave Designer software.
Phillips-head screwdriver.
Flat-head screwdriver.
1. You receive the ControlWave Micro in a box.
Remove it from the box.
2. The ControlWave Micro has three base housing
configurations (3-slot, 4-slot, and 8-slot) and three
expansion housing configurations (2-slot, 4-slots,
and 8-slot). This document discusses the 4-slot
base housing and the 4-slot expansion housing. For
Part D301761X012
Page 2
+70°C
amb
®
Windows
®