Descargar Imprimir esta página

Bosch FLM‑420‑I2‑D Notas De Seguridad página 9

Ocultar thumbs Ver también para FLM‑420‑I2‑D:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 10
Input Interface Module DIN Rail Type
Detected line conditions with
overall line resistance
R
 = R
 + R
 + R
Σ
L/1
L/2
EOL
Contact monitoring
Max. monitoring current
Duration of detectable signal
Detected line conditions with
overall line resistance
R
 = R
 + R
 + R
Σ
L/2
L/2
Con
Voltage monitoring
Voltage range
Input resistance
Low and high thresholds selectable in FSP-5000-RPS
with:
low threshold < high threshold
overall line resistance R
Notice!
Electrical data for the built-in short circuit isolator according to EN 54-17:2005, you find in
F.01U.003.287 FLM-I 420-S Installation Guide.
Bosch Sicherheitssysteme GmbH
< 800 Ω short-circuit: supervisory alarm, interruption: trouble
> 1500 Ω and <6000 Ω standby
> 12000 Ω short-circuit: trouble, interruption: supervisory alarm
Undetermined: 800 Ω up to 1500 Ω, 6000 Ω up to 12000 Ω
8 mA (line short-circuit)
300 ms
Closed: < 800 Ω
Open: > 1500 Ω
Undetermined: 800 Ω up to 1500 Ω
 = R
 + R
 ≤ 50 Ω
Σ
L/2
L/2
Installation Guide
0 to 30 V DC
> 50 kΩ
0.8 V DC (± 0.3 V DC)
3.3 V DC (± 0.3 V DC)
10.2 V DC (± 0.5 V DC)
21.2 V DC (± 0.5 V DC)
Technical specifications | en
2018.11 | 6 | F.01U.012.988
9

Publicidad

loading