Descargar Imprimir esta página

Meccanica Fadini Elpro 7 RP Manual Del Usario página 5

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Elpro 7 RP
GB
Preliminary notes to learning mode:
- make sure that the gate is closed
- make sure that the gate stops in the respective open and closed gate positions
are firmly fixed to the ground.
1
st
1
operation:
cut off power supply to Elpro 7 RP by removing the 2 A - 24 V
low voltage white fuse, which is on the right upper side of
the PCB.
2
nd
2
operation:
hold the button P pressed and re-power the PCB by inserting
the 24 V low voltage fuse back into its holder.
3
rd
3
operation:
when the Led L7 illuminates, release button P: Led L7 will flash 5 times and the
flashing lamp will illuminate: the program "learning working times" has been
entered.
IMPORTANT: at this stage two options are allowed to go on with setting
ie. learning the required operating times: by the P button or by remote
!
control. The last option allows the installation agent to have direct visual
control of the operation being performed by the gates.
4
th
4
operation:
a pulse to open starts M1 motor (the first gate
starts opening).
The time passing from 4
the gate delay time in open cycle, with the options in service (dip No.
!
6 = ON) or out of service (dip No. 6 = OFF, the time is stored but no delay
will occur).
5
th
5
operation:
a pulse to open starts M2 motor (second gate
starts opening).
6
th
6
operation:
a pulse stops M1 motor (first gate wide open on
open gate stop).
ELECTRONIC CONTROL PANEL FOR NUPI 66
WITH PROGRAMMABLE RADIO TECHNOLOGY
L7
L7
L7
M2
th
th
to 5
operations is stored by the system as
M2
M2
7
th
7
operation:
A pulse stops M2 motor (second gate wide open
on open gate stop).
The time passing from 7
dwell time, in service on AUTOMATIC MODE (dip No. 3 = ON) or out of
!
service (dip No. 3 = OFF, dwell time still in the system memory but not
applicable).
8
th
8
operation:
a pulse to close starts M2 motor (M2 gate starts
closing).
The time between the 8
!
as gate delay time on closing cycle.
9
th
9
operation:
L7
a pulse to close starts M1 motor (M1 gate starts
closing).
10
M1
th
10
operation:
a pulse stops M2 motor (M2 gate on closed gate position). In order to ensure
that the gate is securely held in stop position, it is advised to pulse the actuator ie.
gate to stop approx. 3-4 seconds after the gate has reached the end of the permitted
stroke on the closed gate stop position.
11
M1
th
11
operation:
A pulse stops M1 motor (M1 gate on closed gate position). In order to ensure
M1
that the gate is securely held in stop position, it is advised to pulse the actuator ie.
gate to stop approx. 3-4 seconds after the gate has reached the end of the permitted
stroke on the closed gate stop position.
th
The 11
operation concludes the procedure for the control panel to learn the
required working times.
After the learning procedure it is possible to set the operating modes either ON/OFF
as required by means the dip-switches on the PCB.
5
M2
th
th
to 8
operation is stored by the system as
M2
th
th
and 9
operations is stored by the system
M2
M2
M1
M2
M1
M1
M1
M1

Publicidad

loading

Productos relacionados para Meccanica Fadini Elpro 7 RP