2.6 CONDENSATION DRAIN KIT FOR OUTDOOR UNIT
In the outdoor units with heat pump, condensation is created when running in heating mode.In this case it may be necessary to convey
the condensation towards a drain.
To do so, proceed as follows:
1.
Fix the supplied fitting (part 1 - "fig. 9 -") in the appropriate hole (part 2 - "fig. 9 -") on the base of the outdoor unit.The fastening
is carried out by inserting the shaped part of the fitting in the hole.
2.
Connect the fitting ("fig. 10 -") to a sufficiently resistant rubber hose (so that it is not deformed or throttled in any way).
3.
Secure it with a hose clip and route it to an appropriate drain.
4.
Make sure that the pipe slopes enough to allow the condensation to flow down naturally.
5.
Check the efficiency of the drain by pouring a small amount of water directly into the tray of the outdoor unit.
N.B.: The kit is supplied with the machine.