Installation Instructions
1. Product selection
Check kit selection with cable diameter dimension in Tables 1 & 2.
Table 1: Primary Insulation on1/C Solid Dielectric Cable to 1kV
Nominal
Kit
Cable Range
CRSM-34/10
#8-2/0
CRSM-53/13
3/0-400
CRSM-84/20
500-1000
CRSM-107/29
1000-2000
Table 2: Outer Jacket (Sheath) Repair and General Use
Kit
Diameter Range
CRSM-34/10
0.25-1.20" (6-30mm)
CRSM-53/13
0.60-1.80" (15-46mm)
CRSM-84/20
0.95-2.70" (24-69mm)
CRSM-107/29
1.30-3.60" (33-91mm)
CRSM-143/36
1.65-4.95" (42-126mm)
CRSM-198/55
2.50-6.50" (64-165mm)
2. Determine the minimum length of CRSM needed
Damage
+
Dimension A
Up to 3"
3" (75mm)
3" to 12"
4" (100mm)
12" to 24"
6" (150mm)
Over 24"
8" (200mm)
3. Mark cut length of CRSM
Lay the CRSM on a flat surface. Measure the required length of
CRSM using a straight edge (preferably a square) and mark along
the line to be cut. Cut-line must be as nearly square to the rails as
practical.
4. Cut the CRSM to required length
Cut the CRSM using tin snips, large scissors, or a sharp knife. Cut
edges must be smooth, not jagged.
If a knife is used, support the CRSM on a flat surface
and use a straight edge guide.
5. Trim flap; cut channel to length
For neater installation, trim the overlap flap as shown.
Cut or break the channel 1/2" (10mm) longer than the CRSM.
Remove sharp corners and burrs from the channel. If longer than
one channel, lay end to end before measuring.
PII 51068
Revision AD
Diameter Range
0.25-0.60" (6-15mm)
0.60-0.95" (15-24mm)
0.95-1.40" (24-36mm)
1.30-2.00" (33-51mm)
Cut Length of CRSM = Damage + Dimension A
Channel
2
Damage
Mark
1/2"
(10mm)
PCN 121979-000
Effective Date: October 19, 2010