Table 2: Tone indicator
Test/
Alignment
Signal
tone switch
Beam
ON
alignment
Auto-gain
___
lock
Walk test
ON
Alarm
ON
memory
Response time changeover function
See Figure 14.
Response time (sec.). 1. Response 0.05 sec: running. 2.
Response 0.3 sec: walking quickly; 3. Response 0.7 sec:
walking.
This feature is used to modify the response time of the beam to
best suit the application. The unit doesn't detect passing
objects faster than the set response time.
Alarm output
Select N.O. or N.C. signal output. Contact capacity 30
VAC/VDC, 1A or less.
Environmental module
The environmental signal is initiated if the beam reception level
is reduced by poor weather conditions (dense fog or torrential
rain etc.).
N.C. or N.O. signal output is selectable. Initial factory setting
N.C.
Contact capacity 30 VAC/VDC, 1A or less.
Alarm memory function
See Figure 16.
The alarm memory LED shows which sensor has triggered
when two or more sensors are placed on a zone. Connect
P/N 1070011 • REV C • ISS 19MAR19
Other
Description
condition
Lock spacer
Reception strength
detached
monitored.
Tone pitch increases as
reception improves.
Note:
No tone is given if
sensitivity attenuation
LED is lit or if the lock
spacer is attached.
About 5 sec.
Short tone indicates lock
after the lock
is set.
spacer is
Continuous tone (20 sec.)
attached.
indicates readjustment.
For approx.
Tone is linked to alarm
5 min. after
LED.
gain is
Both trip simultaneously.
locked.
Set to
"Beep" is indicated if
manual
alarm condition occurs.
memory.
power (+) to the Alarm memory terminal (Figure 2, position 15)
to activate this function. This circuit works as an external
control switch. An audible tone can also be selected. Reset
can be automatic or manual.
Auto reset:
The memory LED will light for five minutes after an
alarm signal and then continues to flicker for 55 minutes before
returning to normal mode. If additional alarm signals are
triggered, the process repeats.
Manual:
The memory LED lights with the reset button switched
over. The memory is reset manually by a rest button open (L)
or closure (H). The reset button can be placed in any
convenient location on the premises.
Tone alarm with LED:
If an audible signal desired in
conjunction with the memory LED, turn the alignment tone
switch to ON.
Note:
If the alarm memory function is not used, set the
memory selector to "manual" and leave the receiver terminal
unconnected.

External dimensions

See Figure 17.
Troubleshooting
Problem
Possible cause
Operation
No power supply.
LED does
not light.
Bad wiring connection or
broken wire (short).
Alarm LED
No power supply.
does not
light when
Poor wiring connection or
the beam is
broken wire (short).
broken.
Beam is reflected on to
another object and sent
to the receiver.
Four beams are not
broken simultaneously.
The beam interruption
time is shorter than the
set response time.
Alarm LED
Beam alignment is out.
continues
Shading object between
to light.
the transmitter and the
receiver.
Unit optics are dirty.
Frequency channel is not
compatible between the
transmitter and the
receiver.
Intermittent
Bad wiring connection.
alarms
Change of supply
voltage.
Remedy
Turn on the power.
Check and correct the wiring.
Turn on the power.
Check and correct the
wiring.
Remove the reflecting
object or change the beam
direction.
Break four beams
simultaneously.
Adjust the beam response
time.
Check and adjust again.
Remove the shading
objects.
Clean the optics with a soft
cloth.
Readjust to the same
channel.
Check again.
Stabilize supply voltage.