Descargar Imprimir esta página

Liberty Pumps HT40 Serie Manual De Instalación página 5

Bombas sumergibles de alta temperatura

Publicidad

Idiomas disponibles

Idiomas disponibles

Pump runs or hums,
but does not pump.
Pump runs
periodically when
fixtures are not in
use.
Pump operates
noisily.
 NOTE: Liberty Pumps, Inc. assumes no responsibility for damage or injury due to disassembly in the field. Disassembly,
other than at Liberty Pumps or its authorized service centers, automatically voids warranty.
Liberty Pumps, Inc. warrants that pumps of its manufacture are free from all factory defects in material and workmanship
for a period of 3 years from the date of purchase. The date of purchase shall be determined by a dated sales receipt
noting the model and serial number of the pump. The dated sales receipt must accompany the returned pump if the date
of return is more than 3 years from the "CODE" (date of manufacture) number noted on the pump nameplate.
The manufacturer's obligation under this Warranty shall be limited to the repair or replacement of any parts found by the
manufacturer to be defective, provided the part or assembly is returned freight prepaid to the manufacturer or its
authorized service center, and provided that none of the following warranty-voiding characteristics are evident.
The manufacturer shall not be liable under this Warranty if the product has not been properly installed; if it has been
disassembled, modified, abused or tampered with; if the electrical cord has been cut, damaged or spliced; if the pump
discharge has been reduced in size; if the pump has been used in water temperatures above the advertised rating, or
water containing sand, lime, cement, gravel or other abrasives; if the product has been used to pump chemicals or
hydrocarbons; if a non-submersible motor has been subjected to excessive moisture; or if the label bearing the serial,
model and code number has been removed. Liberty Pumps, Inc. shall not be liable for any loss, damage or expenses
resulting from installation or use of its products, or for consequential damages, including costs of removal, reinstallation or
transportation.
There is no other express warranty. All implied warranties, including those of merchantability and fitness for a particular
purpose, are limited to three years from the date of purchase.
This Warranty contains the exclusive remedy of the purchaser, and, where permitted, liability for consequential or
incidental damages under any and all warranties are excluded.
Discharge is blocked or restricted.
Check valve is stuck closed or
installed backwards.
Gate or ball valve is closed.
Total lift is beyond pump's
capability.
Pump impeller is jammed or volute
casing is plugged.
Check valve was not installed, is
stuck open or is leaking.
Fixtures are leaking.
Foreign objects in the impeller
cavity.
Broken impeller.
Worn bearings.
Piping attachments to building are
too rigid.
©Copyright 2012 Liberty Pumps Inc. All rights reserved
Check the discharge line for foreign material,
including ice if the discharge line passes
through or into cold areas.
Remove check valve(s) and examine for
freedom of operation and proper installation.
Open gate or ball valve.
Try to route piping to a lower level. If not
possible, a larger pump may be required.
Consult the factory.
 Remove the pump from the basin. Detach the
pump base and clean the area around the
impeller. Reassemble and reinstall.
Remove check valve(s) and examine for
freedom of operation and proper installation.
Repair fixtures as required to eliminate leakage.
 Remove the pump from the basin. Detach the
pump base and clean the area around the
impeller. Reassemble and reinstall.
Consult the factory for information regarding
replacement of impeller.
Return pump to the factory or authorized repair
station for repair.
Replace a portion of the discharge line with
rubber hose or connector.