ROUTINE MAINTENANCE
A.
Examine the points of the spikes on all three legs. If the flat of any spike exceeds 1/16" (1.5mm) diameter, it must
be replaced. The spikes are assembled with a thread -locking agent, when replacing the spikes, use a thread-locking
agent such as Loctite #222, Permabond LM 113 or equivalent.
B.
The shut-off valve may need to be serviced with a new ball and seat if the valve becomes hard to operate.
Contact Customer Service for a replacement kit if required.
C.
If the spring loaded elevation mechanism becomes hard to operate, clean internal components with rubbing
alcohol. Do NOT use any type of lubrication. This will have an adverse effect.
D.
Check trunions on ball outlet to ensure they are tight before and after each use. If loose, remove, apply
loctite 277 and retighten to 25 ft - lbs.