Rectifying faults
9
Rectifying faults
Note
If you have detailed questions on the specifications of the invert-
er please contact WAECO.
Fault
No output voltage
Warning signal during opera-
tion
Warning sound during opera-
tion below nominal load
The device switches on and
off repeatedly
The inverter switches off
when the consumer is
switched on
24
Cause
No contact to the battery
Battery voltage less than 11 V
(SP162/SP352) or 22 V
(SP164/SP354)
Overheating
Defective fuse (in the inverter
or the vehicle)
The battery voltage is less
than 11 V (SP162/SP352) or
22 V (SP164/SP354)
Poor contact to the battery
Insufficient battery power.
Inadequate cable connection
(cross section too small or
poor contact).
Excessive constant load
Starting current too high
SinePower
Remedy
Check contact and cable.
Charge the battery (start the
engine).
Switch off power consuming
devices.
Let the inverter cool down
and ensure better ventilation.
Have an electrician change
the fuse.
Charge the battery.
Clean the contacts.
Charge the battery.
Use a cable with a larger
cross section and check con-
tacts.
Reduce the load.
Compare the device power
with the maximum power of
the inverter.