No. Parameter
Function
Name
Explanation
33
Maximum allowable
power loss time
34
Freq Searching Min base block time d0.3 - d05.0 s
35
Function
Speed search
Setting
deactivation
current level
36
Reference Freq. Reference freq.
Upper/Low
upper limit
37
Limit Setting
Reference freq.
lower limit
38
Multi-function
Multi-func input(M1) d00:Fwd/Stop, Rev/Stop control
39
Input Terminal Multi-func input(M2) d01:Fwd/Rev, Run/Stop control
40
Function
Multi-func input(M3) d02:3-wire operation control mode
41
Multi-func input(M4) d03:External fault: N.O. input
42
Multi-func input(M5) d04:External fault: N.C. input
43
Analog Meter
Selects frequency
Output Select
or output current for
display on external d01:Analog current meter (0-250%
analog meter
44
Analog Output Analog output gain d01 - d200%
Gain
select
45
Multi-Function Multi-function out-
Output TerM.
put term. 1 (MO1)
Parameter
Value
d0.3 - d05.0 s
d30 - d200%
d0.1 - d400. Hz
d0.0 - d400. Hz
d05:RESET control
d06:Multi-step speed control 1
d07:Multi-step speed control 2
d08:Multi-step speed control 3
d09:Jog frequency control
d10:Accel/decel speed inhibit
d11:1st or 2nd accel/decel time
d12:External baseblock (N.O.)
d13:External baseblock (N.C.)
d14:Up frequency command
d15:Down frequency command
d16:Run PLC Program
d17:Pause PLC Program
d18:External counter trigger input
d19:Counter Reset
d20:(not used)
d00:Analog frequency meter (0 to
[maximum output frequency])
of the rated drive output [A])
d00:AC drive operational
11
Factory
Setting
d2.0
d0.5
d150
d400.
d0.0
d00
d05
d06
d07
d08
d00
d100
d00