Danfoss VLT MICRO Manual Del Usuario página 16

Ocultar thumbs Ver también para VLT MICRO:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 67
No. Parameter
Function
Name
Explanation
66
Master Freq.
67
Frequency
Skip frequency 1
68
Setting
Skip frequency 2
69
Prohibited
Skip frequency 3
70
Freq. Band-
Skip freq. Band
width Setting
Prevention
71
PWM Carrier
Carrier frequency
Frequency
select
72
Auto Reset/Restart Oper. After Fault d00 - d10
73
Fault Records Most recent fault
record
74
2nd most recent
fault record
75
3rd most recent
fault record
76
Key
Key
Parameter
parameter
77
Auto Decel.
Auto deceleration
Gain Key
gain key
VLT
Parameter
Value
d0.1 - 400 Hz
d0.0 - d400. Hz
d0.0 - d400. Hz
d0.0 - d400. Hz
d0.1 - d20.0 Hz
d0.1 - d20.0 Hz
d01 - d18; fc = 1kHz ~ 18kHz
d00:Fault records clear (No
errors occurred)
d01: Over-current (oc)
d02: Over-voltage (ov)
d03: Overheat (oH)
d04: Overload (oL)
d05: Overload 1 (oL1)
d06: External fault (EF)
d07: CPU failure 1 (CF1)
d08: CPU failure 3 (CF3)
d09: Hardware protect failure (HPF)
d10: O.C. during acceleration (oCA)
d11: O.C. during deceleration (ocd)
d12: O.C. during steady state (ocn)
d13: Ground fault or fuse fail (GFF)
d14: EEROM abnormal 2 (CF2)
d15: Manufacture used diagnostics
d16: Manufacture used diagnostics
d17: External baseblock (bb)
d18: Overload 2 (oL2)
d19: Manufacture used diagnostics
d20: Soft protection efficient (codE)
d00: All parameters can always be
set and read
d01: All parameters are read-only
d02 - d09: not used
d10:Resets all parameters to the
factory defaults
d00: Auto deceleration gain key
d01: Able to adjust the gain value
14
®
MICRO
Factory
Setting
d1.0
d0.0
d0.00
d0.00
d0.00
d15
d00
d00
d00
d00
d00
d00

Publicidad

Tabla de contenido
loading

Tabla de contenido