MODEL 8142 FRESH AIR VENTILATOR
OUTLET
MOUNTING
COLLAR
BRACKET

SAFETY INSTRUCTIONS

1. 120 Volts may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power
disconnected until installation/service is completed.
2. Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling duct work.
1. Read all instructions before beginning installation.
2. Improper installation may cause property damage or injury. Installation, service, and maintenance must be performed by a qualified service
technician.
TABLE OF CONTENTS
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction and Compliance Statement . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Install Electrical Outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ventilator Location and Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mount the Ventilator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mount Intake Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Install Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Model 8142NC - Wiring to Various Controls . . . . . . . . . . . . . . . . . . . . . . . . .5
Model 8142NC - Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
10012436 B2207655B 6.19
Model 8142 and 8142NC
Fresh Air Ventilator
Installation and Operating Instructions
VENTILATION
CONTROLLER
INLET
COLLAR
WARNING
CAUTION
READ AND SAVE THESE INSTRUCTIONS
MODEL 8142NC FRESH AIR VENTILATOR
OUTLET
MOUNTING
COLLAR
BRACKET
Model 8142NC - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Model 8142 - Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Model 8142 - Set Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Model 8142 - Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Model 8142 - Rater/Inspector Verification . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1
Model 8142 - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VENTILATION
TERMINALS
INLET
COLLAR
English 1

Publicidad

Capítulos

Tabla de contenido
loading

Resumen de contenidos para Aprilaire 8142

  • Página 1: Tabla De Contenido

    Model 8142 – Wiring the Control to the HVAC System . . . . . . . . . . . . . . .
  • Página 2: Introduction And Compliance Statement

    ASHRAE 62 . 2 -2010 is met as the control adds ventilation time as needed to account for the fractional on-time and effectiveness of the ventilation schedule . The control will also ensure that ventilation occurs no less than one hour of every four . When properly installed and set, the Model 8142 and...
  • Página 3: Ventilator Location And Orientation

    VENTILATOR LOCATION AND ORIENTATION Choose a location for the ventilator that is within 6 feet of the outlet into which the ventilator will be plugged . The ventilator must be installed with the round inlet duct collar facing up or down, or the oval outlet collar must face up . DO NOT install with the outlet collar positioned as shown in FIGURE 2E or 2F, or the integral backdraft damper will not function properly .
  • Página 4: Mount Intake Hood

    • A Model 6506 powered, normally closed damper must be installed in the inlet duct . • Remove the damper from the Model 8142 or 8142NC . Simply open the damper and push on the blade to pop it out of the collar, then remove the blade .
  • Página 5: Model 8142Nc - Wiring To Various Controls

    (see FIGURE 6 on page 4), an additional transformer may be required if the HVAC system transformer does not have enough capacity to power a damper (10 VA required, use Aprilaire part number 4010 if needed) . Select the diagram that corresponds to the control to be used and whether an additional transformer is needed for a separate damper .
  • Página 6: Model 8142Nc - Test Mode

    FIGURE 9 – WIRING TO MODEL 8120A FIGURE 9A – WIRING TO MODEL 8120A AND DAMPER MODEL 8120A DIGITAL VENTILATION CONTROLLER* MODEL 8120A DIGITAL VENTILATION CONTROLLER* POWER INPUTS OUTPUTS POWER INPUTS OUTPUTS USED VENT USED VENT 24 VAC 24 VAC 120 VAC VENT 24 VAC, 10VA...
  • Página 7: Model 8142 - Wiring The Control To The Hvac System

    MODEL 8142 – WIRING THE CONTROL TO THE HVAC SYSTEM NOTICE FIGURE 11 – REMOVE CONTROL FROM MOUNTING PLATE Disconnect power to HVAC system during wiring to avoid electrical shorts. CONTROL 1. Remove the control from the mounting plate as shown in FIGURE 11 .
  • Página 8: Model 8142 - Connecting The Control To The Ventilator

    MODEL 8142 – CONNECTING THE CONTROL TO THE VENTILATOR If the 8142 ventilator is ducted to the supply side of the HVAC system (see FIGURE 5 on page FIGURE 14 – PLUG THE CONTROL INTO THE VENTILATOR 4), plug the Control Connector into the back of the control at the location shown in FIGURE 14 .
  • Página 9: Model 8142 - Set Up

    Select button is used enter the value and move on to the next Set Throughout the Set Up Menu, the Up Menu item . TABLE 1 – MODEL 8142 SET UP MENU TABLE 1 – MODEL 8142 SET UP MENU Menu Item...
  • Página 10: Model 8142 - Test Mode

    TABLE 2 – MODEL 8142 TEST MODE MENU Test Sequence Description Shows - - - - °F to indicate that no separate outdoor temperature sensor has been installed . Model 8142 installations do not require a °F HC % separate sensor – outdoor temperature is measured by the control's on-board sensor .
  • Página 11: Model 8142 - Rater/Inspector Verification

    (Floor Area ft .01) + (No. of Bedrooms + 1) MODEL 8142 – SEQUENCE OF OPERATION “CODE” SETTING The control will turn on ventilation with a heating, cooling or fan call for the set number of minutes during a one-hour cycle period . If the outdoor temperature is above the high temperature ventilation limit, ventilation will not occur with a cool or fan call, but if it is below the low temperature ventilation limit it will occur with a heat call .
  • Página 12: Limited Warranty

    WARRANTY REGISTRATION Visit us online at www.aprilaire.com to register your Aprilaire product . If you do not have online access, please mail a postcard with your name, address, phone number, email address, product purchased, model number, date of purchase, and dealer name and address to: Research Products Corporation, P . O . Box 1467, Madison, WI 53701 .
  • Página 13: Instrucciones De Seguridad

    Introducción y declaración de cumplimiento . . . . . . . . . . . . . . . . . . . . . . . .2 Modelo 8142: cableado del control al sistema de HVAC . . . . . . . . . . . . . . 7 Especificaciones .
  • Página 14: Introducción Y Declaración De Cumplimiento

    INTRODUCCIÓN Y DECLARACIÓN DE CUMPLIMIENTO El ventilador de aire fresco modelo 8142 y 8142NC de Aprilaire® está diseñado para incorporar de manera precisa la cantidad correcta de aire del exterior a las viviendas actuales diseñadas eficientemente . Conduzca la entrada del ventilador a una entrada de aire exterior y conduzca la descarga al sistema de HVAC; luego, simplemente enchufe la unidad, configure la cantidad de ventilación necesaria y seleccione los límites de temperatura deseados .
  • Página 15: Ubicación Y Orientación Del Ventilador

    UBICACIÓN Y ORIENTACIÓN DEL VENTILADOR Seleccione una ubicación para instalar el ventilador que se encuentre a menos de 6 pies del tomacorriente en el que enchufará el ventilador . El ventilador se debe instalar con el anillo redondo de conducto de entrada hacia arriba o abajo, o el anillo ovalado de salida debe mirar hacia arriba . NO instale con el anillo de salida colocado como se muestra en la FIGURA 2E o 2F, o el regulador de contracorriente integral no funcionará...
  • Página 16: Instalación Del Extractor De Admisión

    • Se debe instalar un regulador normalmente cerrado accionado por energía modelo 6506 en el conducto de admisión . • Retire el regulador del modelo 8142 o 8142NC . Simplemente abra el regulador y presione la paleta para que salga del anillo; luego, retire la paleta .
  • Página 17: Modelo 8142Nc: Cableado Para Varios Controles

    El ventilador de aire fresco modelo 8142NC se puede conectar al termostato modelo 8620 o 8620W de Aprilaire, al sistema de control de IAQ modelos 8910, 8910W o 8920W de Aprilaire, o al controlador digital de ventilación modelo 8120A o 8120X . Si el ventilador está conectado por conductos al lado de retorno del sistema de HVAC y se instala un regulador separado (consulte la FIGURA 6 de la página 4), es posible que se necesite un transformador adicional si el transformador del sistema...
  • Página 18: Modelo 8142Nc: Modo De Prueba

    FIGURA 9: CABLEADO DEL MODELO 8120A FIGURE 9A: CABLEADO AL MODELO 8120A Y AL REGULADOR CONTROLADOR DIGITAL DEL SISTEMA DE VENTILACIÓN MODELO* CONTROLADOR DIGITAL DEL SISTEMA DE VENTILACIÓN MODELO 8120X* ALIMENTACIÓN ENTRADAS SALIDAS ALIMENTACIÓN ENTRADAS SALIDAS USAR VENT USAR VENT 24 V de CA VENTILADOR 120 V de CA DE 24 V de CA...
  • Página 19: Modelo 8142: Cableado Del Control Al Sistema De Hvac

    MODELO 8142: CABLEADO DEL CONTROL AL SISTEMA DE HVAC AVISO FIGURA 11: RETIRO DEL SISTEMA DE CONTROL DE LA PLACA DE MONTAJE Desenchufe el sistema de HVAC durante el cableado para evitar que ocurran cortocircuitos eléctricos. 1. Retire el sistema de control de la placa de montaje tal como se muestra en PLACA DE la FIGURA 11 .
  • Página 20: Modelo 8142: Cómo Conectar El Control Al Ventilador

    MODELO 8142: CÓMO CONECTAR EL SISTEMA DE CONTROL AL VENTILADOR Si el ventilador 8142 está conectado al lado de suministro del sistema de HVAC (consulte la FIGURA 5 FIGURA 14: CONEXIÓN DEL SISTEMA DE CONTROL AL VENTILADOR de la página 4), enchufe el conector de control a la parte trasera del control en la ubicación que se muestra...
  • Página 21: Modelo 8142: Configuración

    Select (Seleccionar) se utiliza para ingresar el valor y continuar con En el menú de configuración, los botones el siguiente elemento del menú de configuración . TABLA 1: MENÚ DE CONFIGURACIÓN DEL MODELO 8142 TABLA 1: MENÚ DE CONFIGURACIÓN DEL MODELO 8142 Elemento del menú...
  • Página 22: Modelo 8142: Modo De Prueba

    Descripción °F Muestra - - - - °F para indicar que no se instaló ningún sensor de temperatura exterior independiente . Las instalaciones del modelo 8142 no requieren un HC % sensor independiente: la temperatura exterior se mide con el sensor incorporado del sistema de control .
  • Página 23: Modelo 8142: Verificación Del Evaluador/Inspector

    MODELO 8142: VERIFICACIÓN DEL EVALUADOR/INSPECTOR Para verificar la configuración del tiempo de ventilación, presione el botón Select (Seleccionar) para desplazarse por las opciones de Required Continuous CFM (CFM constantes necesarios) y Measured CFM (CFM medidos) calculados para esta instalación . Si algún valor no coincide con el valor esperado, se debe ingresar al menú de configuración para modificar la superficie cubierta, la cantidad de habitaciones o los CFM medidos .
  • Página 24: Garantía Limitada

    GARANTÍA LIMITADA El ventilador de aire fresco de Research Products Corporation de Aprilaire® cuenta con una garantía de cinco (5) años a partir de la fecha de instalación que cubre defectos materiales o de mano de obra . La obligación exclusiva de Research Products Corporation bajo esta garantía es la de suministrar, sin cargo, un repuesto para cualquier pieza que esté dañada dentro del período de los cinco (5) años mencionado y usted o su proveedor original puede devolverlo hasta treinta (30) días después del período de 5 (cinco) años a Research Products Corporation, Madison, Wisconsin...