Duration of compressor ON time in the
case of faulty ambient probe
(emergency mode).
If CE1=0 the emergency mode in the
CE1
presence of error E0 remains disabled, the
compressor remains off and defrosting is
prevented in order to conserve the remaining
cold.
Duration of compressor OFF time in the
CE2
case of faulty ambient probe.
(emergency mode).
Compressor safety time for door switch:
when the door is opened the evaporator fans
doC
shut down and the compressor will continue
working for time doC, after which it will shut
down.
Compressor
opening. When the door is opened and after
tdo time, it's setted back the normal
functioning giving door open alarm (Ed)
tdo
If the door switch is closed and the light
stays on for a longer time than tdo light cell
alarm is signaled (E9).
With tdo=0 the parameter is disabled.
FAN shutdown TEMPERATURE
The fans will stop if the temperature value
Fst
read by the evaporator sensor is higher
than this value.
Fd
Fst differential
LSE
Minimum value attributable to setpoint.
HSE
Maximum value attributable to setpoint.
AU1
Auxiliary/alarm relay 1 control
AU2
Auxiliary/alarm relay 2 control
StA
Temperature setting for auxiliary relay
ECP 202 EXPERT – Parameters Abstract
Pag. 4
restart
time
after
door
-45 ÷ (HSE-1) °C
(LSE+1) ÷ +99°C
-6 (NC) = relay de-energised during stand-by.
-5 (NC) = Contact for casing element control
(AUX relay closed with compressor
output inactive).
-4 (NC) = pump down function (NC, see CHAP
5.16).
-3 (NC) = automatic auxiliary relay managed
by StA temp. setting with 2°C differential
(NC).
-2 (NC) = manual auxiliary relay controlled via
AUX key (NC).
-1 (NC) = alarm relay (NC).
0 = relay deactivated.
1 (NO) = alarm relay (NO).
2 (NO) =manual auxiliary relay controlled via
AUX key (NO).
3 (NO) = automatic auxiliary relay managed
by StA temp. setting with 2°C differential
(NO).
4 (NO) = pump down function (NO, see CHAP
5.16).
5 (NO) = free voltage contact for condensing
unit (AUX relay and compressor relay in
parallel).
6 (NO) = relay excited during stand-by.
0 ÷ 240 min
0 = disabled
5 ÷ 240 min
0 ÷ 5 min
0 ÷ 240 min
0 = disabled
-45 ÷ +99 °C
1 ÷ +10 °C
(like AU1 )
-45 ÷ +99°C
Rev. 01-19
0 min
5 min
0 min
0 min
+99 °C
2 °C
-45 °C
+99 °C
-1
5
0 °C