Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 32
Full Programming Options

Menu Structure

Quickstart >
Tel. Numbers >
Alarm no.1
Alarm no.2
Alarm no.3
Alarm no.4
Tech.no.
Background no.
Call attempts
Settings
>
ID Code
Volume
System Config >
HW Monitoring >
Delays
>
COP delay
AS delay
Tech IP delay
Hangup delay
Answer delay
Redial del.
VAD timeout
Messages
>
Location
Reassurance
Guidance
Time/Date
>
Time
Date
Advanced
>
Passcode
Network ID
Next EN81 call
PBX Frequency
Language
Relay mode >
Relay override>
GMT Offset
Templates
Load Template
Save Template
Del. Template
Menu Sections explained...
HW Monitoring
Hardware monitoring sets which system elements are checked whe the
unit completes its self-check and places a test call. Default settings are
shown below:
HW Monitoring >
Delays
The delays can be set to alter the length of the delay before the
unit places a call.
COP delays - How long (in seconds) each of the alarm buttons, in
the COP, needs to be pressed before an emergency call is placed.
Default is 3 seconds
AS delay - Local voice alarm station (LVAS) and remote alarm
station (RAS). How long (in seconds) each of the alarm buttons
needs to be pressed before an emergency call is placed. Default is
3 seconds.
Tech delay - Relates to the delay before a technical call is placed,
upon receiving a fault signal from a connected third party device
using Technical Input.
Hang up delay - Sets time (in minutes) before C100 hangs up a call
(talk time).
>
Answer delay - the number of rings the C100 must detect before
answering any incoming calls. Where multiple C100 are sharing a
line, they must all have the same Answer Delay set.
Redial del. - Sets a delay (in seconds) between the C100 dialling
different numbers. A setting of 0 (the default setting) will de-
activate this feature.
VAD Timeout - Sets a time out (in seconds) whereby if the C100
does not detect voice on the line it will automatically terminate the
call. A setting of 0 (the default setting) will de-activate this feature.
Quick dial
Reduces the dial tone detection test
from 7 seconds to 3 seconds – prevents
issues with exchanges timing out after 4
seconds.
Quick VAD
Allows the C100 to detect speech before
the first ring pulse has been sent down
the line,
Dialtone req.
Requires the C100 to detect a dial tone
before it attempts to dial out.
Lineflt. Alert
If the phone line to the C100 is cut,
the unit will play an audible warning
message. The message will repeat every 3
minutes unit the phone line is restored.
Power Supply
Battery
Phone Line
Spkr/mic.
AS
GSM Status

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Memco c100 sm2Memco c100 sm3

Tabla de contenido