MANUAL DE INSTRUCCIONES
Date/Time
Control
Logs
Reject change
Validate change
J
.P. SELECTA s.a.u.
CÓDIGO 80381 REV A
Setting screen
Icons meaning:
Set time and date
Press on the time/date icon. Press successively on the box to select
the days, months, years, minutes, seconds adjustment.
Adjust by pressing on the icons to increase and decrease.
Set control
With a value of the appropriate P, I, D parameters, the cabinet will reach
the temperature in the shortest possible time and without exceeding
the set temperature. However, those values can be quite different at
high and low temperatures.
These values can be modified, but it's advisable to perform an «Auto-
tunning» when you need a better accuracy.
The «Autotunning» automatically adjusts the optimal parameters for a
given temperature and load.
Press on the Control menu. Press successively on the box to select
the P, I, D values adjustment and modify the value by pressing on the
increase and decrease icons.
Attention: It is not reccommended to change these parameters. Use
the «Autotunning» option to automatically adjust these values.
Press on the Control menu.
Select the «Autotunning» temperature with:
(it is recommended to set the most used temperature). There are two
calculation methods that are identified with 100 or with 40. The 100
method has a slower duration, but it is more accurate. For most appli-
cations, 40 method is more than enough.
Start «Autotunning» by pressing on the icon
If for some reason you want to stop, press on:
Ctra. NII Km 585.1 Abrera 08630 (Barcelona) España
e-mail:selecta@jpselecta.es - web site: www.jpselecta.es
FEBRERO 2020
Temperature
Units
Language (Spanish, English,
French)
Up/Down
Tel 34 937 700 877 Fax 34 937 702 362
Pag.: 22