3.5.1.5 Examples
examples of settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
on
DS-5 AES
off
DS-4 Ch. current
on
DS-3 Ch. current
off
DS-2 St.-alone mode
off
DS-1 St.-alone mode
off
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in: 50A
5 AES: off
4, 3 Charging current: 75%
2, 1 Stand-alone mode
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP
switches, see appendix A, position J). The overload and low-battery LEDs will flash to indicate acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
3.5.2 Step 2: Other settings
The remaining settings are not relevant (na) for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
ds8-ds7
voltage
14.1
off
off
28.2
56.4
14.4
off
on
28.8
57.6
14.7
on
off
29.4
58.8
15.0
on
on
30.0
60.0
ds6: absorption time 8 or 4 hours (na for L2, L3)
ds5: adaptive charging characteristic (na for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (na for L2, L3)
(the wide input frequency range (45-55Hz) is 'on' by default)
Note:
-
If "adaptive charging algorithm" is on, ds6 sets the maximum absorption time to 8 hours or 4 hours.
-
If "adaptive charging algorithm" is off, the absorption time is set to 8 hours or 4 hours (fixed) by ds6.
12
DS-8
on
DS-8
DS-7
on
DS-7
DS-6
on
DS-6
DS-5
off
DS-5
DS-4
on
DS-4
DS-3
on
DS-3
DS-2
off
DS-2
DS-1
off
DS-1
Step1, stand-alone
Step1, stand-alone
Example 2:
Example 3:
8, 7, 6 AC-in: 50A
8, 7, 6 AC-in: 16A
5 AES: off
5 AES: off
4, 3 Charge: 100%
4, 3 Charge: 100%
2, 1 Stand-alone
2, 1 Stand-alone
Float
Storage
voltage
voltage
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
off
DS-8
on
on
DS-7
on
on
DS-6
off
DS-5
on
on
DS-4
on
DS-3
on
off
DS-2
off
DS-1
Step1, stand-alone
Example 4:
8, 7, 6 AC-in: 30A
5 AES: on
4, 3 Charge: 50%
2, 1 Stand-alone
Suitable for
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV)
Gel MK battery
Gel Victron Deep Discharge
Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
Tubular plate traction batteries in
semi-float mode
AGM spiral cell
Tubular plate traction batteries or
OPzS batteries in cyclic mode
on = 8 hours off = 4 hours
on = active
off = inactive
(inactive = fixed absorption time)
on = active
off = inactive
on = active
off = inactive
on = 115V
off = 120V
on = 50Hz
off = 60Hz
off