The module must be connected to the control panel via a 2 pole twisted-
shielded cable. This cable carries both the power supply and the two-way digital
communications data. Refer to the Installation section for the wiring diagram.
The module has a short-circuit isolator which, in the event of short-circuit
between the two poles of the control panel loop cable, is capable of
interrupting the negative pole and thus isolating the section involved in the
short-circuit. For the isolator specification, please refer to the "ILP
Specification" document.
The module should be housed inside an electrical mounting box, as per the
diagram, with the following characteristics:
• Minimal internal dimensions: 100 x 60 x 40 mm
• Protection grade IP44 or higher
• Compliant with the established standards and codes relating to the Installation of
electrical systems
The two removable serial number stickers should be taken off
the module; one should be attached to the box where the
device is to be housed, the other to the installation layout.
Once all the loop devices have been properly connected, refer to the control
panel installation and programming manual for instructions regarding the
configuration and addressing procedures.
The functionality of the module should be tested immediately after installation and periodically during
maintenance inspections, in accordance with the established standard regulations and codes in force.
The EITK-DRV driver allows you to change the operating parameters of the devices connected to the loop and
also to obtain accurate diagnostic data. It can operate through the USB port of a computer furnished with the
relative software programme, or can function autonomously by way of the battery housed inside.
For further information and details regarding use of the EITK-DRV driver, refer to the respective handbook.
The EM411R module must be used exclusively with control panels that operate on INIM OpenLoop protocol. This
product is not suitable for outdoor installation. However, if outdoor installation is necessary, ensure that the
device is housed inside a suitable enclosure with the required protection grade.
INIM Electronics reserves the right to change
the technical specifications of this product
without prior notice.
4
NO1 NC1 C1
NO2 NC2 C2
Installation
Testing and maintenance
Using the EITK-DRV driver
Warnings and limitations