SC130
TECHNICAL CHARACTERISTICS
Power supply
Working time
No. of motors
Pause time
Courtesy light time
Photocells power supply
Operating temperature
Courtesy light / Flasher
Learnable transmitters
Transmitters receiver
Limit switch
INSTALLATION WARNINGS
Before proceeding with the installation, it is necessary to fit a magneto-thermal and differential switch of 10A max.
upstream of the system. The switch must guarantee an omnipolar separation of the contacts, with an opening
distance of at least 3 mm.
Differentiate and keep the power cables (min. section 1,5mmq) separated from the signal cables, that can
be 0,5mmq.
WARNINGS:
• During wiring, the control unit must not be powered.
• The use of this control unit must follow and strictly respect the technical standards of reference.
• The installation and/or maintenance must be carried out only by qualified personnel, in compliance with regulations
in force.
• The manufacturer cannot be considered responsible for possible damages caused by improper and/or
unreasonable use.
• A wrong installation or use of the product can compromise the safety of the system.
• All the materials contained in the package must be kept away from children, since they pose a potential risk.
230 VCA single-phase 50/60 Hz (F1-5A)
Adjustable 7-120s (JP1open) with trimmer TL
Adjustable 7-40s (JP1 close) with trimmer TL
Sum between working time and pause time both after Open and after Close
WARNING: IMPORTANT SAFETY INSTRUCTIONS.
It is important for the safety of persons to follow these instructions.
Keep this instruction manual.
1 x 500W
3-200s with trimmer TP
12VDc 2W (F2-500mA restorable)
-20 +55 °C
230V 100W
30
Built-in, not replaceable
Inputs FCA and FCC in terminal board
9
UK