Wiring
Always disconnect the power supply before making any connections.
The power supply circuit should be connected with a minimum 2 A, 230 V, switch located close to the unit. Power
supply cables should be H05VV-F or H05V-K. The gauge will depend on local regulations, but should in no case be
2
less than 1 mm .
Cables for connecting the relay contact should have a sufficient gauge for the equipment to be connected.
For connecting the pushbutton, use a V3V3-F type cable with three 0,5 mm wires minimum and an insulation
voltage of 300/500 V. The maximum distance is 100 m.
AKO-52067
ALARM STATION
BASIC
PUSHBUTTON
AKO-52068
ALARM STATION
BASIC
PUSHBUTTON
Power supply connection
and alarm output
8A
1
2
3
4
5
C
NO
NC
230 Vac
ALARM
Input
output
Max. 100 mts
Power supply connection
and alarm output
8A
1
2
3
4
5
C
NO
NC
230 Vac
ALARM
Input
output
Max. 100 mts
Cable not
included
Jumper wire necessary
10
2
Pushbutton
input
6
7
8
Cable not
included
Pushbutton
input
6
7
8
5206H701 Ed.03
+12Vcc
GND