Descargar Imprimir esta página

LAMBORGHINI FL LOW NOX 24 MCA Instrucciones De Uso, Instalación Y Mantenimiento página 16

Publicidad

Idiomas disponibles

Idiomas disponibles

4.2 Startup
Before lighting the boiler
Check the seal of the gas system.
Check correct prefilling of the expansion tank.
Fill the water system and make sure all air contained in the boiler and the system
has been vented.
Make sure there are no water leaks in the system, DHW circuits, connections or boil-
er.
Check correct connection of the electrical system and efficiency of the earthing sys-
tem.
Make sure the gas pressure for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
Checks during operation
Switch the unit on.
Check the tightness of the fuel circuit and water systems.
Check the efficiency of the flue and air/fume ducts while the boiler is working.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water
production stages.
Check correct boiler lighting by performing various tests, turning it on and off with
the room thermostat or remote control.
Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap. 5.
Make sure that with no demand for heating, the burner lights correctly on opening a
hot water tap. Check that in heating mode, on opening a hot water tap, the heating
circulating pump stops and there is regular production of hot water.
Make sure the parameters are programmed correctly and carry out any required
customisation (compensation curve, power, temperatures, etc.).
4.3 Maintenance
Periodical check
To ensure correct operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:
The control and safety devices (gas valve, flow meter, thermostats, etc.) must func-
tion correctly.
The fume exhaust circuit must be perfectly efficient.
(Sealed chamber boiler: fan, pressure switch, etc. -The sealed chamber must be
tight: seals, cable glands, etc.)
(Open chamber boiler: anti-backflow device, fume thermostat, etc.)
The air-fume end piece and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits. For possible cleaning
do not use chemical products or wire brushes.
The electrode must be properly positioned and free of scale.
=
=
fig. 12 - Electrode positioning
The gas and water systems must be airtight.
The water pressure in the cold water system must be about 1 bar; otherwise, bring
it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must correspond to that given in the respective tables.
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation, press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to eliminate
the fault.
Faults marked with the letter "F" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
16
EN
List of faults
Table. 2
Fault
Fault
code
A01
No burner ignition
Flame present signal with
A02
burner off
Overtemperature protec-
A03
tion activation
Fume thermostat activated
(after activation of the fume
F04
thermostat, boiler operation
is prevented for 20 minutes)
F05
Card parameter fault
No flame after the ignition
A06
phase
F07
Card parameter fault
A09
Gas valve fault
F10
Delivery sensor 1 fault
F11
DHW sensor fault
F14
Delivery sensor 2 fault
A16
Gas valve fault
F20
Card parameter fault
A21
Card parameter fault
A23
Card parameter fault
A24
Card parameter fault
F34
Supply voltage under 180V. Electric mains trouble
F35
Faulty mains frequency
Incorrect system water
F37
pressure
F39
External probe fault
A41
Sensor positioning
F42
Heating sensor fault
F43
Exchanger protection trips.
F50
Gas valve fault
cod. 3541D130 - Rev. 01 - 03/2018
FL LOW NOX 24 MCA
Possible cause
Cure
Check the regular gas flow to the
No gas
boiler and that the air has been elimi-
nated from the pipes
Check the wiring of the electrode and
Ignition/detection electrode fault
that it is correctly positioned and free
of any deposits
Check the gas valve and replace it if
Faulty gas valve
necessary
Gas valve wiring disconnected
Check the wiring
Ignition power too low
Adjust the ignition power
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
Check the correct positioning and
Heating sensor damaged
operation of the heating sensor
No water circulation in the system Check the circulating pump
Air in the system
Vent the system
Fume thermostat contact open
Check the thermostat
Wiring disconnected
Check the wiring
Flue obstructed or not correctly
Check the flue
sized
Check the card parameter and modify
Wrong card parameter setting
it if necessary
Low pressure in the gas system
Check the gas pressure
Burner minimum pressure setting Check the pressures
Check the card parameter and modify
Wrong card parameter setting
it if necessary
Wiring disconnected
Check the wiring
Check the gas valve and replace it if
Faulty gas valve
necessary
Sensor damaged
Check the wiring or replace the sen-
Wiring shorted
sor
Wiring disconnected
Sensor damaged
Check the wiring or replace the sen-
Wiring shorted
sor
Wiring disconnected
Sensor damaged
Check the wiring or replace the sen-
Wiring shorted
sor
Wiring disconnected
Wiring disconnected
Check the wiring
Check the gas valve and replace it if
Faulty gas valve
necessary
Check the card parameter and modify
Wrong card parameter setting
it if necessary
Check the card parameter and modify
Wrong card parameter setting
it if necessary
Check the card parameter and modify
Wrong card parameter setting
it if necessary
Check the card parameter and modify
Wrong card parameter setting
it if necessary
Check the electrical system
Electric mains trouble
Check the electrical system
Pressure too low
Fill the system
Water pressure switch damaged
Check the sensor
or not connected
Check the wiring or replace the sen-
Probe damaged or wiring shorted
sor
Probe disconnected after activat-
Reconnect the external sensor or dis-
ing the sliding temperature
able the sliding temperature
Delivery sensor or DHW sensor
Check the correct positioning and
detached from the pipe
operation of the sensors
Sensor damaged
Replace the sensor
No system H
O circulation
Check the circulating pump
2
Air in the system
Vent the system
Modulating Operator wiring dis-
Check the wiring
connected
Check the gas valve and replace it if
Faulty gas valve
necessary

Publicidad

loading