Modes Cont.
Autonomous Mode
Autonomous mode means that the device can be installed as a "fit and forget" solution and will send an alert to the Avire
Hub if issues occur. This mode self learns periods of activity and tests the lift depending on the average usual usage of
the lift. If the lift is not active when it usually should be busy the device will assume a fault with the elevator and will run
an automated test of the elevator.
Autonomous mode features 3 sensitivity's, Low – High, Low sensitivity and Medium sensitivity only test the elevator if it
is inactive during usually busy periods, High sensitivity will anticipate busy periods and test the elevator before a busy
period to confirm activity. Note High sensitivity will also test the lift if a perceived fault is present as Medium sensitivity
does.
Blocked Time Period Mode
Blocked Time Period mode means that the device can not be tested during the selected time. This mode overwrites all
other modes and the lift will not be tested even if Lift Hawk is notices that the lift is inactive in the period that is usually
busy.
Required Time Mode
Required Time mode means that the device can be configured to perform tests at specific day and time, and will send
an alert to the Avire Hub if issues occur. This mode can be configured by the user and allows to choose days in the week
and set specific time for the test. The test can be performed once a day only, as an example, user can set the device to
do test on Monday, Wednesday, Friday every week at 5 in the morning or set to have daily tests at any specific time of the
day.
Triggering Remote Test
Memcom System
To trigger a remote call when wired to a Memcom Emergency Phone System the following steps should be used.
Step
Step 1.
Step 2.
Step 3.
Step 4.
Step 5.
The remote test is now active, if there is a no motion detected from your remote test, a fault call will be placed back to
the Technical Fault call number specified in your Memcom
Technical Support
If you require any further assistance when programming the HAWK unit, please call our Technical Service Team.
www.avire-global.com
Action
Phone your Memcom number
Enter Menu
Trigger Lift Test
Turn Trigger Off
Exit Menu