Thank you for purchasing the haupa
The device can be used with DC and AC voltages of between 6 V and 400 V, and for polarity testing.
®
The haupa
„Basic" carries a protection rating, making it suitable for use in harsh conditions.
You have selected a device that is designed to offer you a high degree of safety. It conforms to
IEC/EN 61010 standards. In order to ensure that the unit is operated correctly and safely, read these
operating instructions thoroughly BEFORE operating the device.
The following safety precautions should be observed:
1. Check the voltage tester for correct functioning immediately before each use (as per VDE
specification 0105, part 1), by connecting it to a known voltage source (e.g. a 230V power
socket). If the indicator shows that one or more functions are not working correctly, do not use
the device any further, but have it examined by a qualified service technician. You can contact
our works service department for this purpose.
2. Always hold the device by its handles.
3. Avoid touching the probe tips.
4. Note that all testing for no voltage should be carried out at two poles.
5. The voltage indications on the haupa
6. Trouble-free operation can only be guaranteed at temperatures of between -10°C and +50°C.
7. Keep the device clean and dry at all times. The casing may be cleaned by wiping with a damp
cloth.
1.)DC voltage testing:
When the probe tips are connected to a DC voltage that lies within the rated voltage range, one of the
lower (6V + -) or bottom LED indicators lights up to indicate the corresponding voltage. The upper LED
indicators show the voltage, whereby the reference pole is connected to the large hand element.
2.)AC voltage testing:
When the probe tips are connected to an AC voltage that lies within the rated voltage range, both of
the upper (6V + -) and the lower LED indicators light up to indicate the corresponding voltage.
Simultaneous lighting up of the upper LEDs indicates the presence of an AC voltage.
3.) Phase search:
Hold one test tip against the earth (ground) lead and use the other tip to check the remaining leads.
®
The haupa
„Basic" indicates the AC voltage for the phase in question. FI/RCD is not triggered.