Troubleshooting Guide - DIY D12 Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Troubleshooting Guide

If problems arise with the Tapemat to perform electrical work, it is highly recommended that
a qualified, licensed electrician be hired.
Although this troubleshooting guide is provided to assist with problems experienced with a
floor heating system, results are never guaranteed. TapeMat does not assume any liability or
responsibility for damage or injury that may occur from using this guide. If problems with the
system persist, call the manufacturer.
Any electrical troubleshooting work should be performed with the power removed
from the circuit, unless otherwise noted.
Problem
An analog meter (using a moving
needle) was used to take the reading.
If measurement shows an open or
short circuit, the Heating Wire has
If measurement is just a little low or
Mat resistance
high, room temperature has affected
measurement is
outside the range
The resistance measurement could
printed on the
be from more than one mat wired in
nameplate label.
series, or wired in parallel. Either will
provide false resistance readings.
The multi-meter may be set to the
GFCI has tripped, indicated by a
light or "GFCI TRIP" on the control.
Floor is not
getting warm.
Mats are wired in "series" or "daisy
Possible Cause
been damaged.
the resistance.
wrong scale.
Mat has been damaged.
Incorrect voltage supplied,
or mismatched electrical
components used.
Uninsulated concrete slab floor.
chained" (end-to-end).
Obtain a digital multi-meter and re-measure the
Record resistance between all wires and contact the
Make the room temperature 65°– 75°F (18°-24°C),
or contact the manufacturer.
Make sure resistance measurements are for only one
The multi-meter should typically be set to the 200
ohms (200Ω) scale. For mats with resistance range
higher than 200 ohms on the nameplate label, set the
meter to the 2000 ohm (2kΩ) scale.
Measure mat resistance. Check for both "open circuit"
and "short circuit" as detailed earlier in this manual.
If damaged, record resistances between all wires and
contact the manufacturer.
Check for loose wire connections. Reset the GFCI on the
control or circuit breaker. If it trips again, check for a
short circuit in the mat as detailed earlier in this manual.
If mat is damaged, record resistance between all wires
and contact the manufacturer. If mat is not damaged,
replace the GFCI control. Also see "GFCI conflicts" below.
Measure "line" voltage, then measure "load" voltage.
120 VAC mats have black and white power leads. 240
VAC mats have black and blue power leads.
Surface temperatures rise slowly an uninsulated slab
and heat is lost to the ground below.. If, after 5 to 8
hours of heating, the floor is not warmer to the touch,
check for mat damage (see "Mat has been damaged"
above). A clamp-on ampmeter may be used to verify
the amps are correct to each mat.
Multiple mats must be connected in "parallel"
(or black-to-black, white-to-white).
29 of 96
Solution
resistance.
manufacturer.
mat at a time.
©2015 SunTouch

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido