Wayne WCP85 Manual De Instrucciones De Operación página 3

Unidad de condensación
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
(Continued)
STEP 5: INSTALLATION OF SAFETY
SWITCH (IF APPLICABLE)
Safety switch is only
to be used on Class 2
circuit, 30V AC, 3.2 amps maximum.
Connect power cord
to a constant
voltage source. Do not connect to a fan
or other device that may run
intermittently.
A. The pump can be wired directly to
the appliance thermostat to shut
the appliance down in the event of
pump failure. Refer to Figure 6 for
typical wiring diagram.
NOTE: The alarm can be wired in the
safety switch at the normally open
("NO") contact.
TIPS FOR EASY INSTALLATION
1. After reading instructions, check to
make sure installation does not exceed
a maximum of 15 feet of
vertical lift.
2. Make sure pump is level. No part of the
pump base should be more than
1/8" off of level plane.
3. Use soapy water on unit when
performing cleaning maintenance.
(Refer to Maintenance guidelines.)
4. For optimum performance, drain and
discharge lines should have a
continuous downward slope. Test
operation of pump to make sure lines
have enough downward slope for
efficient operation.
5. Avoid overtightening of check valve
after cleaning. (Refer to Maintenance
gudelines.)
6. Use constant voltage power source. Do
not plug into a device that runs
intermittently.
7. Locate model number and date code on
pump and take note of them.
8. To assure proper performance, the
highest point of discharge line should
be higher than 5' off the floor.
9. Clean any debris in the pump reservoir
if necessary.
Insert tubing or pipe
through inlet of pump
until this tip makes
contact with the
bottom of reservoir.
Figure 3 - Modification of pipe end to prevent blockage
High efficiency
gas furnace
Condensate Neutralizer
Cartridge (If Required)
Main Drain from Furnace
Figure 4 - Plumbing pipe from drain to inlet holes on pump
3/8" ID Tubing
Hose clamp
(recommended, not included)
Figure 5 - Installation of discharge line
3
Diagonally cut 3/8 tube
at approximately 45°.
Main Drain from Coil
Overflow
Drain from Furnace
Inverted "U"
15 Ft.
Max
Model WCP85
Drain Pipe
Overflow Drain from
Coil When Required
GFCI
Outlet
Do not kink or pinch
To Main Drain
GFCI
Outlet
www.waynepumps.com