Configuration
group B DIP Switches
Select AC Sharing—OPTIONAL
B2
B1
Your Inverter/Charger features a high-output battery charger that can draw a significant amount of AC power from your utility source or
generator when charging at its maximum rate. If your unit is supplying its full AC power rating to its connected heavy electrical loads at the
same time as this high charging occurs, the AC input circuit breaker could trip, resulting in the complete shut off of pass-through utility
power.
To reduce the chance of tripping this breaker, all APS Inverter/Chargers may be set to automatically limit the charger output. This keeps the sum
of the unit's AC load and charge power within the circuit breaker rating. This charger-limiting function has two settings, allowing you to
reduce the charger's draw lower and lower, as needed, if the AC input circuit breaker keeps tripping under the normal AC loads of devices you
have connected downline from the unit. The figures show how to set your DIP Switches for charger-limiting.
Select Battery Charger-Limiting Points—OPTIONAL
"Most Limiting" (#B2 & #B1 Up):
Charger-limiting takes effect the moment
any 120V AC load is applied; charger
output falls gradually from full output at no
120V load passing through to no output at
full load.
"Least Limiting" (#B2 Down & #B1 Up):
Charger-limiting begins when the Inverter/
Charger's load reaches 66% of the Inverter/
Charger's load rating. Charger output falls
gradually from full output at 66% of the
Inverter/Charger's load rating to about 66% of full output at full load.
Select Equalize Battery Charge—OPTIONAL
B3
This DIP Switch is momentarily engaged
to begin the process of equalizing the
charge state of your battery's cells by time-
limited overcharge of all cells. This can
extend the useful life of certain types of
batteries; consult with your battery's manufacturer to determine if
your batteries could benefit from this process. The charge
equalization process is automatic; once started, it can only be
stopped by removing the input power.
Set Battery Charging Amps—OPTIONAL
B4
Check the nameplate for your unit's high-
and low-charging amp options. By setting
on high charging, your batteries will charge
at maximum speed. When setting on low
charging, you lengthen the life of your
batteries (especially smaller ones).
(continued)
(factory setting)
"Less Limiting" (#B2 Up & #B1 Down):
Charger-limiting begins when the Inverter/
Charger's load reaches 33% of the Inverter/
Charger's load rating. Charger output falls
gradually from full output at 33% of the
Inverter/Charger's load rating to about 40% of full output at full
load.
"No Limiting" (#B2 & #B1 Down): No
charger-limiting occurs at any load size.
Setting Procedure
• Move to "Equalize" (DOWN) position for three seconds.
• Move to "Reset" (UP) position and leave it there. This is the
factory default setting.
CAUTION: Do not leave DIP switch #B3 in the down position after beginning process. Battery
charge equalization should only be performed in strict accordance with the battery manufacturer's
instructions and specifications.
Battery Charge
Reset
Equalize
Battery Charger
Low Charge Amps
High Charge Amps
CAUTION: When switching to the High Charge Amp setting, the user must ensure that the
amp hour capacity of their battery system exceeds the amperage of the High Charge Amp
setting or the batteries may be damaged or degraded.