8 • SETTINGS AND FUNCTIONS VIA REMOTE CONTROLE (FIG. 4)
NoTE: To get the best possible reception, point the remote control
at the detector during programming. Please note that if the sun
shines directly onto the sensor, the standard detection range of
approximately 8 m may be reduced by the sun's infrared rays.
Temporary functions
The functions are carried out as soon as the button has been
pressed, but they are not stored.
Button
Customised setting
Switch oN/oFF manually
End the "test"/manual light oN/oFF/time setting function
Return to preset mode
The channel remains permanently switched on during test mode
When each movement is detected, regardless of
the ambient lighting level, the blue mode LED flashes
twice. To exit, press the "Reset" button.
Programming
The following functions can only be programmed when the device is
in programming mode. All changes are stored and the functions are
implemented after exiting programming mode.
Enter programming mode
The blue LED lights up and indicates programming
mode. The light channel switches on. The detector's
movement sensor is disabled whilst the device is in
programming mode.
Exit programming mode
The blue LED goes out; the settings are now stored.
The detector will now operate automatically
according to the preset values.
NoTE: If programming mode is not exited by
pressing the button, the detector automatically
exits programming mode 10 minutes after the
last button was pressed. All functions set up
until this point will be stored.
Setting the brightness set value (10 lux...800 lux)
Acknowledgement: the red and blue LEDs flash
3 times.
Daytime operation setting (2,000 lux)
Acknowledgement: the red and blue LEDs flash
3 times (channel 1), no light measurement,
light is only activated by presence.