General Information; Technical Specifications - BFT LEO B CBB 3 400 W01 Instrucciones De Instalación

Ocultar thumbs Ver también para LEO B CBB 3 400 W01:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 31

2) GENERAL INFORMATION

The LEO B CBB 3 400 W 01 control panel comes with standard factory settings.
Any change must be made using the programmer with built-in display or universal
handheld programmer.
Its main features are:
-
Control of 1 three-phase motor
-
Electronic torque control
-
Separate inputs for safety devices
-
Configurable command inputs
-
ENCODER control input
The board has a terminal strip of the removable kind to make maintenance
or replacement easier. It comes with a series of prewired jumpers to make the
installer's job on site easier.
The jumpers concern terminals: 70-71, 70-72, 70-74, 76-77.
If the above-mentioned terminals are being used, remove the relevant jumpers.
TESTING
The LEO B CBB 3 400 W 01 panel controls (checks) the start relays and safety
devices (photocells) before performing each opening and closing cycle.
If there is a malfunction, make sure that the connected devices are working
properly and check the wiring.
The control panel power supply must be protected by 3 fuses 10x38
500V"aM". Choose the type of fuses which will be triggered in case of motor
seizure.
Terminal
Definition
L1
L2
L3
N
NEUTRAL
10
11
12
20
LIGHT 230V
21
AUX 3 - FREE CON-
26
TACT (N.O.)
(Max. 24V 3W)
27
40
- REF SWE
41
+ REF SWE
42
A RS485
43
B RS485
50
51
52
24 Vsafe+
60
Common
61
62
63
Common
64
65
70
Common
71
72
73
FAULT 1
74
75
FAULT 2
76
Common
77
78
FAULT 3
Y
ANTENNA
#
14 -
LEO B CBB 3 400 W 01
INSTALLATION MANUAL
LINE 1
LINE 2
Three-phase Power supply 400V~ ±10%, 50-60Hz.
LINE 3
U
V
Three-phase motor connection
W
Flashing light 230V output max. 40W.
Contact N.O. (24V~/3W max).
Can only be used with second channel of radio-receiver plugged into relevant connector.
ENCODER power supply
ENCODER communication
24V-
Accessories power supply output.
24V+
Tested safety device power supply output (photocell transmitter and safety edge transmitter).
Output active only during operating cycle.
IC 1 and IC 2 inputs common
Configurable command input 1 (N.O.) - Default START E.
IC 1
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Configurable command input 2 (N.O.) - Default PED.
IC 2
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
IC 3 and IC 4 inputs common
Configurable command input 3 (N.O.) - Default OPEN.
IC 3
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Configurable command input 4 (N.O.) - Default CLOSE.
IC 4
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
STOP, SAFE 1 and SAFE 2 inputs common
The command stops movement. (N.C.)
STOP
If not used, leave jumper inserted.
Configurable safety input 1 (N.C.) - Default PHOT.
SAFE 1
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2
Refer to the "Safety input configuration" table.
Test input for safety devices connected to SAFE 1.
Configurable safety input 2 (N.C.) - Default BAR.
SAFE 2
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2
Refer to the "Safety input configuration" table.
Test input for safety devices connected to SAFE 2.
SAFE 3 input common
Configurable safety input 3 (N.C.) - Default PHOT OP.
SAFE 3
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST
Refer to the "Safety input configuration" table.
Test input for safety devices connected to SAFE 3.
Antenna input.
Use an antenna tuned to 433MHz. Use RG58 coax cable to connect the Antenna and Receiver. Metal bodies close to the antenna
can interfere with radio reception. If the transmitter's range is limited, move the antenna to a more suitable position.
SHIELD

3) TECHNICAL SPECIFICATIONS

Power supply
Low voltage/mains insulation
Operating temperature range
Thermal overload protection
Dielectric rigidity
Maximum motor power
Accessories power supply
AUX 3
Flashing light
Dimensions
Fuses
Protection rating
(*other voltages to order)
4) TERMINAL BOARD WIRING Fig. B
Description
400V~ ±10%, 50-60Hz*
> 2MOhm 500V
-10 / +55°C
built into motor
mains/LV 3750V~ for 1 minute
980W
24V~ (demand max. 180mA)
24V~safe (demand max. 180mA)
NO contact (24V~/max.3W)
230V~ 40W max
see Fig. A
see Fig. B
IP54