Balluff BTL7-A/C/E5 Serie Manual De Instrucciones página 43

Ocultar thumbs Ver también para BTL7-A/C/E5 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 101
BTL7-A/C/E5 _ _ -M _ _ _ _ -SF-F _ _
Magnetostrictive Linear Position Sensor – Rod Style
8
Adjust (continued)
Set end point
► Bring float to the new end point.
► Press
b
for at least 2 s.
⇒ The new end point is set with the last valid
end value.
Adjust end value
► The end value can be changed using
gradient of the curve changes
(see page 14).
► End calibration procedure: Briefly press
simultaneously (< 1 s).
⇒ Set position value is saved.
End adjustment
► Briefly press
a
and
simultaneously (< 1 s).
b
⇒ The current position value is displayed once the
buttons are released.
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
www.balluff.com
> 2 s
a
a
a
and
b
. The
b
b
a
and
b
< 1 s
< 1 s
Displayed values (example)
At 0...10 V
9.89 V
b
10.00 V
10.00 V
8.00 V
2.00 V
a
b
8.00 V
10.50 V
a
b
7.63 V
english
At 4...20 mA
19.13 mA
20.00 mA
20.00 mA
16.80 mA
6.00 mA
16.80 mA
3.60 mA
18.56 mA
17

Publicidad

Tabla de contenido
loading

Tabla de contenido