2.3. Opening of the End limit switch setting mode:
- Press simultaneously on ▲ and ▼ for 3 seconds. The motor will run briefly in one direction and
then in the in the other*. Go to step 2.4.
2.4. Initializing obstacle detection:
- Press on ▲ for 3 seconds. The motor will run briefly in one direction and then in the other*. Go to
step 2.5.
2.5. Adjustment of down end limit:
The use of rigid link (VAR, VAS, EASYLINK, OctoEasy) allows an
automatic adjustment of the Down end limit in accordance with the
blocking provided by the rigid link. If you use it, go directly to step
2.6, otherwise proceed to the following operations:
1. Position the motor on the desired down end limit using the ▲ and ▼ keys.
2. To memorize the down end limit, press ▲ twice, as folow:
- 1
press: for 0,5 second without the motor rotation.
st
- 2
press: over 3 seconds, so the motor rotates briefly one way, then the other*. Go to step 2.6.
nd
2.6. Adjustment of up end limit:
The use of bottom slat stopper will allows an automatic adjustment of the up end limit in accordance with the blocking provi-
ded by the stopper. If you use it, go directly to step 2.7, otherwise proceed to the following operations:
1. Position the motor on the desired up end limit using the ▲ and
▼ keys.
2. To memorize the up end limit, press ▼ twice, as follow:
- 1
press for 0,5 second without the motor rotation.
st
- 2
press over 3 seconds, so the motor rotates briefly one way,
nd
then the other*. Go to step 2.7.
2.7. Validation of end limits:
- Press the ▲ and ▼ keys simultaneously for at least 3 seconds. The motor will run briefly in one
direction and then in the other*. The settings are now complete. There is not delay time any more.
You can now connect the motor to the final switch (§3).
* Press the buttons until the motor turns into the two directions.
3
Final wiring
- Be careful of the direction of rotation (§2.2).
- Mandatory use of a reversing switch that stops the ▲ and ▼ keys being activated simultaneously.
- Possibility of wiring 3 motors max. in parallel on one switch.
- The length of the cable between the electrical switch and the motor must not exceed 50 m.
- Please do contact SIMU when using KNX / EIB electronic switching control devices.
- Attach cables to prevent any contact with moving parts. If the motor is used outdoors and if the power supply cable is of
the H05-VVF type, then run the cable in a UV-resistant conduit, e.g. trunking.
N
L
PE
1
2
0,5s
>>
2
1
>>
T5E
Blue
Brown
Black
Green/yellow
≥3s
>>
≥3s
>>
≥3s
>>
+
>>
6s max.
0,5s
≥3s
+
>>
>>
6s max.
≥3s
>>
2/3