For a unidirectional communication mode:
Use 1 wired controller to control 1 indoor unit (see Figure 6.9).
When the display board is customized then the wired controller can
be connected in this way.
Indoor unit 1
Figure 6.9
For the specific connection method, refer to the instructions in the
corresponding wired controller manual to carry out the wiring and
connections.
The X1, X2 ports on the sides of the main control board and the
unidirectional communication port (display board side) are for
different types of wired controllers (see Figure 6.10).
(2.2~3.6kW )
X1
X1
X2
X1
To wired controller
To wired controller
comm. bus
comm. bus
Indoor Main Control Board
(RED)
CN12
Figure 6.10
6.4 Handling the Electrical Wiring Connection Points
Once the wiring and connections are done, use tie straps to
secure the wiring properly so that the connection joint cannot be
pulled apart by external force. The connection wiring must be
straight out so that the cover of the electrical box is level and can
be closed tightly.
Use professional insulation and sealing materials to seal and
protect the perforated wires. Poor sealing may lead to
condensation, and entry of small animals and insects that may
cause short circuits in parts of the electrical system, causing the
system to fail.
Display board
A
B
C
D
Wired controller 1
(4.5/5.6kW )
(7.1~9.0kW )
E
P Q
P Q
E
X2
X1
X2
X1
To wired controller
comm. bus
(2.2~9.0kW )
Wired
controller
Display board
7. On-site Configuration
7.1 Address Settings
When this indoor unit is connected to the outdoor unit, the outdoor unit
will automatically allocate the address to the indoor unit. Alternatively,
you may use the controller to manually set the address.
The addresses of any two indoor units in the same system cannot
be the same.
The network address and the indoor unit address are the same,
and does not have to be configured separately.
Once the address settings are completed, mark the address of
each indoor unit to facilitate after-sales maintenance.
The centralized control of the indoor unit is completed on the
outdoor unit. For details, refer to the manual on the outdoor unit.
Caution
Once the centralized control function for the indoor unit has been
completed on the outdoor unit, the DIP switch on main control
panel of the outdoor unit must be set to auto addressing;
otherwise, the indoor unit in the system are not controlled by the
centralized controller.
The system can connect up to 64 indoor units (address 0~63) at
the same time. Each indoor unit can only have one address DIP
switch in the system. The addresses of any two indoor units in
the same system cannot be the same. Units that have the same
X2
address may malfunction.
X2
7.2 DIP Switch Settings on Main Board
ON
SW1
1 2
ON
SW1
1 2
ON
SW1
1 2
ON
SW1
1 2
ON
SW2
1 2
ON
SW2
1 2
ON
SW2
1 2
ON
SW2
1 2
26