3. Specifications

3.1. Specifications
Parameter
U
AC grid voltage
GRID
F
AC grid frequency
GRID
T
Max. operating temperature
MAX
T
Min. operating temperature
MIN
T
Nom. operating temperature
NOM
Relative humidity
Enclosure rating
Acoustic noise
PF
Power factor
I
Total harmonic distortion
THD
Safety class
Galvanic isolation class
Input surge protection
Islanding protection
Islanding detection ENS
Limitation of 10 minutes mean AC
grid voltage
Reverse polarity protection
Overvoltage category
Pollution degree
DC-switch
Galvanic isolation
Table 3.1: General Specifications
Parameter
Input
Nominal input power DC
Max. power DC
Max. recommended PV power at STC
Starting capacity
Power consumption (Off mode)
Power consumption (Standby mode)
Input voltage range (medium voltage)
Input voltage range (high voltage )
Input start-up voltage (medium/high voltage)
Max. input voltage range (medium/high volt-
age)
Individual string configuration
Max. input voltage range (medium/high volt-
age)
Parallel string configuration
Max. input current at 40°C (medium voltage)
Max. input current at 40°C (high voltage )
Independent MPP trackers
Output
Nominal output power
Max. output power (temperature dependent)
Nominal output current
Max. output current
Max. efficiency
European efficiency, Master/Slave
Weight (incl. wall bracket)
Dimensions L×W×H, mm (incl. wall bracket)
Table 3.2: Specification for ULX Inverters
1) Depending on country setting/adjustable.
2) Depending on country setting.
3) For fixed systems with semi-optimal conditions.
*) Max. 16 A per string.
Condition
Settings 50/60 Hz
Nominal power
SWL
P > 20 %
P
NOM
Complete inverter
Communication
interface
Common mode
According to IEC 60 664-1 III
According to IEC 60 664-1 3
Inverter
ULX 1800o
ULX 3000o
1800 W
3000 W
1950 W
3200 W
3)
1950 Wp
3200 Wp
10 A
2 x 10 A *)
7 A
2 x 7 A *)
1
1650 W
2750 W
1800 W
3000 W
6.5 A
11.3 A
8 A
13 A
93.7
94.2
91.6
92.9
17 kg
20 kg
489 × 434 × 192 618 × 434 × 192 618 × 434 × 192 747 × 434 × 192
L00410363-05_2q
3. Specifications
Specification
180-270 V AC
46-55/55-65 Hz
60 °C ambient
-25 °C ambient
40 °C ambient
0-95%
IP 54
55 dBA
0.97
< 5 %
Class I
Class II
4 kV
U/F window
"ENS" acc. to VDE 0126-1-1
Acc. to EN50160
Integrated
Integrated. acc. to VDE 0100-712
Transformer with galvanic isolation
ULX 3600o
ULX 5400o
3600 W
5400 W
3900 W
5850 W
3900 Wp
5400 Wp /
5850 Wp
20 W
<0.2 W
8 W
180 - 350 V
260 - 500 V
125 V / 250 V
450 V / 600 V
410 V / 550V
2 x 10 A *)
3 x 10 A *)
2 x 7 A *)
3 x 7 A *)
2
2
3300 W
4600/5000 W
3600 W
5000/5400 W
13 A
19 / 22 A
15.5 A
94.2
93.4
20 kg
23 kg
3
3
1)
2)
1)
23 A
94.3
93.4
15

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ulx 1800oUlx 3000oUlx 3600oUlx 5400o

Tabla de contenido