CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing
the battery.Service the battery under the supervision of personnel knowledgeable of
batteries and their precautions.
CAUTION! Use only the specified type of battery. See your dealer for replacement
batteries. CAUTION! The battery may present the risk of electrical shock. Do not dispose
of batteries in a fire, as they may explode. Follow all local ordinances regarding proper
disposal of batteries. CAUTION! Do not open or mutilate the batteries. Released
electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN
ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are
removed during installation and maintenance (applicable to a UPS and a remote battery
supply not having a grounded circuit)
BATTERY REPLACEMENT PROCEDURE:
1.Remove the
right-side of the
faceplate.
Remove the retaining screw cover of
4.
the cable connectors.
BATTERY REPLACMENT
2.Remove the three retaining
screws on the cable protection
cover then remove the cover
faceplate.
3.Disconnect
the black and
red cables.
Replace the new battery pack.
5.
Assemble the screws, cable and front
panel in the reserve sequence of
above steps. Recharge the unit for 4-8
hours to ensure the UPS performs
expected runtime.