Inspection Upon Receipt Of Goods; General; Visible Damage; Concealed Damage - Tripp-Lite SU140KMBPK Manual De Operación Y Mantenimeinto

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4. Inspection Upon Receipt of Goods

4.1 General

Special precautions and care have been taken to ensure the system arrives safe and undamaged. However, upon receipt, you should inspect
the entire shipment, including the crate and any boxes, for evidence of damage that may have occurred during transit.

4.2 Visible Damage

It is the responsibility of the person receiving the shipment to inventory and fully inspect all materials against the bill of lading or waybill
IMMEDIATELY while the carrier representative is still present. Ensure that all items are accounted for, including number of skids and quantity
of boxes. Also note any visible external damage that may have occurred during transit. Make all applicable notations on the delivery receipt
before signing and file a damage report with the carrier.

4.3 Concealed Damage

Within 3 to 30 days of receipt (depending on courier), unpack the system and check for any concealed damage. Check the materials
received against the detailed packing list to verify the quantity and the condition as complete and satisfactory.
Note any damage to the internal packaging. Then request an inspection by the carrier and file a concealed damage claim. If there is a
material shortage, visit www.tripplite.com/support to file a claim.
Please contact your shipping company for all shipping damage. Tripp Lite is not responsible for any shipping damage.

4.4 Return of Damaged Goods

Should equipment be damaged and require return to Tripp Lite for repair, a representative will provide instructions along with an RMA number
to expedite the return.
An RMA number must be obtained before returning equipment to Tripp Lite.

5. System Overview

The Tripp Lite SU140KMBPK Maintenance Bypass Panel (MBP) is used in conjunction with an Uninterruptible Power Supply (UPS) to
maintain total continuity of power to connected load circuits when bypass of the UPS equipment is required for performance of regular
service and maintenance.
The SU140KMBPK MBP has a current capacity of 600A with multiple input voltage options available.
The MBP contains three molded-case circuit breakers that are protected by a Kirk Key interlock system.

6. System Specifications

Always refer to the Ratings Label on the equipment for configuration-specific ratings. Equipment specifications and ratings in this
document represent typical equipment and may vary from the equipment provided.

6.1 Electrical

Voltage: 208Y/120VAC, 3-Phase, 4-Wire, plus ground
Frequency: 60 Hz
Current: 600A
Short Circuit Rating: Up to 65 kAIC
Neutral Bus Current Rating: 1000A

6.2 Environmental

Operating Temperature: 32°F to 104°F (0°C to 40°C)
Relative Humidity: 5% to 95% non-condensing
Altitude: 0 to 7400 ft. (0 to 2255 m) above sea level