For information regarding device placement, coverage and method of installation, refer to
the established standard regulations and codes relating to automatic fire-detection systems.
Iris series detectors are compliant with EN54-7: Smoke detectors – Point detectors using the
scattered light principle, light transmission or ionization (ID100 and ID300 models only)
and EN54-5: Heat detectors – point detectors (for ID200 and ID300 models only).
Iris series detectors offer wide-spectrum detection of smoke particles generated by the majority of fires. They
are suitable for most applications and provide first-rate early warning.
The EITK-DRV driver, supplied by INIM Electronics, allows you to change the operating parameters to suit specific
environment conditions. This device permits easy programming and verification of contamination and
performance. For further details, refer to "Using the EITK-DRV driver" section.
During standby status, these detectors have low current draw, 80 A. However, in the event of alarm the current
draw increases to a maximum of 40mA thus signalling the condition to the control panel.
INIM Electronics offers three Iris series conventional fire-detectors, which can be identified by the technical
specifications/serial number on the back of the detector.
Optical detector equipped with a reference chamber based on the scattered light
principle (Tyndall effect). This detector must be installed in draught and obstacle
free place which guarantees appropriate air-flow into the reference chamber.
The detector will trigger an alarm when the level of smoke inside the reference
chamber reaches the following values:
• 0.08 dB/m (mode set via the EITK-DRV)
• 0.10 dB/m (mode set via the EITK-DRV)
• 0.12 dB/m (pre-set mode)
• 0.15 dB/m (mode set via the EITK-DRV)
Heat detector with heat-sensitive element capable of sensing the temperature
within the protected environment.
The operating modes, programmable via the EITK-DRV are:
• "A1R" (pre-set); the detector signals alarm status when the temperature within the protected
environment exceeds 58 °C or when the temperature undergoes anomalous changes.
• "B"; the detector signals alarm status when the temperature within the protected
environment exceeds 72°C.
• "A2S"; the detector signals alarm status when the temperature within in the protected
environment exceeds 58°C.
• "BR"; the detector signals alarm status when the temperature within the protected
environment exceeds 72° or when it senses a rapid temperature rise.
The operating modes of the "A2S" and "BR" are not certified.
Optical-heat detector with heat sensitive element and optical smoke chamber. The
combination of values provides (in accordance with the operating mode selected
via the EITK-DRV driver) high immunity to nuisance alarms and an exceptionally
sensitive detector which is capable of swift response to fires characterized by low
smoke emission.
The operating modes, programmable via the EITK-DRV driver are:
• "PLUS" (pre-set); the detector signals alarm status when smoke in the protected
environment exceeds the programmed threshold (programmed as described for the
ID100 model) or when the temperature within the protected environment exceeds the
Iris
Conventional fire detectors
ID100 - optical smoke detector
ID200 - temperature detector
ID300 - multicriteria detector

Product description

0832-CPR-F1152
0832-CPR-F1243
0832-CPR-F1153
ATTENTION!
ID100
ID100
CONVENTIONAL
OPTICAL SMOKE DETECTOR
EN54-7:2000+A1+A2
0832
0832-CPR-F1152
MADE IN ITALY
*NNNNNNNN*
ID100 NNNNNNNN
ID200
ID200
CONVENTIONAL
CLASS P HEAT DETECTOR
0832
EN54-5:2000+A1
0832-CPR-F1243
MADE IN ITALY
*NNNNNNNN*
ID200 NNNNNNNN
ATTENTION!
ID300
ID300
CONVENTIONAL
MULTI OPTICAL SMOKE AND CLASS P HEAT DETECTOR
EN54-5:2000+A1
0832
EN54-7:2000+A1+A2
0832-CPR-F1153
MADE IN ITALY
*NNNNNNNN*
ID300 NNNNNNNN
0832
991c/01
NNNNNNNN
YYYY/MM
FW: FF.WW
ID100 NNNNNNNN
991e/01
NNNNNNNN
YYYY/MM
FW: FF.WW
ID200 NNNNNNNN
991a/01
NNNNNNNN
YYYY/MM
FW: FF.WW
ID300 NNNNNNNN