Specific function: position the opening
and closing of the 2nd stage fuel oil
valve differently.
The control unit has the possibility of setting
the opening of the 2nd stage valve, when
the 1st stage changes to the 2nd stage, at a
different position to that for closing when the
2nd stage drops to the 1st stage.
- To do this, as described before, first set the
opening position of the 2nd stage fuel oil
valve.
- Lastly position the cursor on the symbol
and confirm with the button
symbol will change like this one
- Using the button
the setting value of the 2nd stage oil fuel
valve, and fix the new closure position, as
described in the paragraph "Modifying the
value of a servomotor position setting".
Closing the "Setting the flame" menu.
The burner setting is now complete. If
necessary, it is possible to again correct
each of the settings values. To do this,
position the cursor on the value to be
modified, using the button
Otherwise, at all times, the following
possible ways of closing the "Setting the
flame" menu are available:
- Returning to the burner settings with
passing through the pre-setting phase
(without entering a password). To do this,
position the cursor on the symbol
confirm with the button
values already saved therefore remain
available.
- Saving the fixed values and ending the
setting procedure. To do this, position the
cursor on the symbol
button
. The burner is then ready to
operate and can now be controlled by the
boiler regulation.
- Quitting the settings menu without
reaching the end of the setting procedure.
To do this, position the cursor on the symbol
and confirm with the button
servomotor positions saved up to this point
are recovered by calling up the settings
menu again.
420010492200
. The selected
.
, position the cursor on
or
.
and
. All the settings
and confirm with the
. All the
Operating mode - Display of the
operating status, the flame signal and
the operating time.
After setting of the burner has been
completed, it switches to operating mode.
The current operation of the burner
(Operation in 1st or 2nd stage) is indicated
by the cursor.
The lower cell shows the intensity of the
signal. The display range is from 0 μA to 13
μA. For the 2nd stage, a good quality signal
is one above 3 μA. The following limit
values are valid:
• When checking an unwanted flame: the
signal must be < 0.7 μA.
• During the safety time: the signal must be
> 1.3 μA.
• During operation: the signal must be > 1.1
μA.
The cell at the bottom right displays the
current operating time of the burner.