Descargar Imprimir esta página

Eaton Moeller DV51-322-025 Instrucciones De Montaje página 13

Publicidad

®
UL
Cautions, Warnings and Instructions
Wiring Warnings for Electrical Practices and Wire Sizes
The Cautions, Warnings, and instructions in this section summarize
the procedures necessary to ensure an inverter installation complies
with Underwriters Laboratories
Warning!
Use 60/75 °C Cu wire only or equivalent.
Warning!
Open Type Equipment.
Warning!
Suitable for use on a circuit capable of delivering not more
than 5,000 rms symmetrical amperes:
• 240 V maximum for DV51-322 and DV51-320 models.
• 480 V maximum for DV51-340 models.
Warning!
"Suitable for use on a circuit capable of delivering not
more than 5,000 rms symmetrical amperes, 480 V
maximum." For DV51-340 models.
Circuit Breaker and Fuse Sizes
The inverter's connections to input power must include UL Listed
inverse time circuit breakers with 600 V rating, or UL Listed fuses as
shown in the table below.
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals
are presented in the table below.
Inverter Model
Input
Voltage
DV51-322-025
200 V
DV51-322-037
DV51-322-055
DV51-322-075
DV51-322-1K1
DV51-322-1K5
DV51-322-2K2
DV51-320-4K0
DV51-320-5K5
DV51-320-7K5
DV51-340-037
400 V
DV51-340-075
DV51-340-1K5
DV51-340-2K2
DV51-340-3K0
DV51-340-4K0
DV51-340-5K5
DV51-340-7K5
h
AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
kcmil = 1,000 circular mils, a measure of wire cross-sectional area
mm
= square millimeters, a measure of wire cross-sectional area
2
Moeller GmbH, Industrieautomation, D-53105 Bonn
© 2005 by Moeller GmbH
®
guidelines.
Motor Output
Fuse
(UL-rated, class J, 600 V)
kW
HP
A
0.2
10
k
0.4
10
m
0.55
10
o
0.75
1
15
1.1
1 m
15
1.5
2
20 (single ph.)
15 (three ph.)
2.2
3
30 (single ph.)
20 (three ph.)
4
5
30
5.5
7 m
40
7.5
10
50
0.4
3
m
0.75
1
6
1.5
2
10
2.2
3
10
3
4
15
4
5
15
5.5
7 m
20
7.5
10
25
Wire Connectors
Warning!
Field wiring connections must be made by a UL Listed and
CSA Certified ring lug terminal connector sized for the wire
gauge being used. The connector must be fixed using the
crimping tool specified by the connector manufacturer.
Cable
Cable support
Motor Overload Protection
Moeller DV51 inverters provide solid state motor overload
protection, which depends on the proper setting of the following
parameters:
• B012 „ electronic overload protection"
• B212 „ electronic overload protection, 2
Set the rated current [Amperes] of the motor(s) with the above
parameters. The setting range is 0.2 * rated current to 1.2 * rated
current.
Warning!
When two or more motors are connected to the inverter,
they cannot be protected by the electronic overload
protection. Install an external thermal relay on each motor.
Wiring Size
Range
AWG
16
16
16
14
14
12
10
12
10
8
16
16
16
16
14
14
12
12
Änderungen
vorbehalten
Terminal (ring lug)
nd
motor"
Torque
ft-lbs
Nm
0.6
0.8
0.6
0.8
0.6
0.8
0.9
1.2
0.9
1.2
0.9
1.2
0.9
1.2
0.9
1.2
1.8
2.5
1.8
2.5
0.9
1.2
0.9
1.2
0.9
1.2
0.9
1.2
0.9
1.2
0.9
1.2
1.8
2.5
1.8
2.5
05/09 AWA8230-2147
NB653XD Doku (05/09)
13/13

Publicidad

loading