ELECTRICAL CONNECTIONS- ZRRK14-EB, ZRRK22-EB, AND ZRRK24-EB
NOTE: The emergency driver must be fed from
the same branch as the AC Driver.
STEP 1:
Using customer supplied 90°C minimum rated wire
connectors, make the following electrical connections:
a. Connect the black luminaire lead to the
unswitched voltage supply lead.
b. Connect the white/red luminaire lead to
the switched supply switched.
c. Connect white luminaire lead to the neutral supply lead.
d. Connect the green ground lead to the incoming ground
lead from the conduit or screw the green ground
lead to the existing troffer pan if the safety ground
is made through the pan on the existing troffer
e. If 0 -10V Dimming is used, connect the violet lead
to the supply positive dimming lead. If dimming is
not being used ensure to cap off the violet lead.
f.
If 0 -10V Dimming is used, connect the grey lead
to the supply negative dimming lead. If dimming is
not being used ensure to cap off the grey lead.
g. Secure incoming dimming leads to the existing strain
relief, to prevent contact with primary wiring.
STEP 2:
Locate the battery female connector to the male connector on the
emergency driver.
© 2020 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content
is subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree
registered trademarks and the Cree SmartCast Technology logo is a trademark of Cree, Inc. SmartCast
trademark of Cree Lighting, A company of IDEAL INDUSTRIES.
5 of 5
***NOTE: Do Not mate male connector from the
emergency driver to the female connector from the
battery until installation is complete and AC power is
supplied
and the Cree logo are
®
, is a registered
®
LUMINAIRE
GREEN OR
GREEN/YELLOW
GROUND
NEUTRAL
WHITE
WHITE
SWITCHED HOT
WHITE/RED
UNSWITCHED HOT
BLACK
DIM (+) VIOLET
VIOLET
DIM (-) GREY
GREY
***MALE CONNECTOR
EB DRIVER
***FEMALE
CONNECTOR
BATTERY
www.creelighting.com
LPN00825X0001A0_C