2. Run main feed into the panel (Figure 2).
WARNING: Electric Shock hazard. May Result in
Serious Injury or Death. To avoid the risk of electric shock,
locate and lock supply breaker in the OFF position before
wiring to power terminal blocks.
Wire strip length should be 9/16 in (13 mm). The main lug will accept
wire up to 2/0 AWG (67 mm
2
14 AWG to 8 AWG (2 mm
6 AWG to 2/0 AWG (13 mm
be fed with a minimum 80 A single-phase feed. The -120L4 panels
should be fed with a minimum 60 A 3-phase feed. All module and
control feed wiring is pre-wired.
3. Install load wiring (Figure 3). Each module controls up to 4 loads.
Label each wire clearly as you wire to the terminal blocks.
NOTE: To install the HW-RPM-4R in 8 module panels, the factory
installed terminal blocks must be replaced with the terminal blocks
supplied with each HW-RPM-4R. Additionally, the factory wiring must
be field modified for each HW-RPM-4R as shown in Figure 3b using
suitable copper 12 AWG (4 mm
NOTE: Wiring for HW-RPM-4M modules will differ. For wiring, refer
to the installation instructions provided with the module. Cap the load
wiring with a wire connector rather than terminating it to the terminal
block. Replacement terminal blocks are provided with these modules.
4. Install module interface feed (Figure 4). Connect the module
interface using the feed plug. This feed will draw a maximum of 2 A.
Lutron recommends that a dedicated feed be used for this purpose.
Leave this circuit breaker off until the module interface is installed.
5. Test all load wiring. Turn on input power to the module locations.
Check all connected lighting to ensure it is on. If a breaker trips, a
wiring error or excessive load exists and must be resolved.
NOTE: The pre-installed bypass jumpers will distribute power to each
load and MUST NOT be removed until after all circuit wiring has been
fully tested and all modules are installed.
6. Install MI mounting screws (Figure 2). If panel is recess (flush)
mounted, install MI mounting screws (provided).
7. Complete panel cover label. Record load names for each zone on
the panel cover label.
8. Install cover. En sure that the cover vents are over the module area.
Tighten cover screws. If a module interface has not been installed,
leave these installation instructions in the panel.
Figure 3 - Module Wiring
3a. HW-RPM-4A, HW-RPM-4U, and
HW-RPM-4FSQ (-8D panels only)
Load
Input Hot from Module Breaker (pre-wired)
Input Neutral from Main Lug (pre-wired)

Customer Assistance

+1.844.LUTRON1 - U.S.A. / Canada / Caribbean
+1.888.235.2910 - Mexico
+1.610.282.3800 - Other Countries
www.lutron.com/support
2
). Tighten lug to 50 in-lb (5.6 N•m) for
2
to 8 mm
) and 120 in-lb (13.5 N•m) for
2
2
to 67 mm
). The -120L3 panels should
2
) wire.
Bypass Jumper
(Do not remove until load
wiring has been tested and
all modules are installed)
Output 1
Output 2
Output 3
Output 4
Load Neutral 1
Load Neutral 2
Load Neutral 3
Load Neutral 4
Torque Terminal Blocks to:
5.3 in-lb to 7.0 in-lb (0.6 N•m to 0.8 N•m)
DO NOT overtighten
Figure 3 - Module Wiring
3b. HW-RPM-4R (HWBP-2S panels only)
Load
Input Hot from Module Breaker (pre-wired)
Load Neutral 1 / Input Neutral from Module Breaker
Load
Input Hot from Module Breaker (pre-wired)
Load
Input Hot from Module Breaker (pre-wired)
Load
Input Hot from Module Breaker (pre-wired)
Torque Terminal Blocks to: 5.3 in-lb to 7.0 in-lb (0.6 N•m to 0.8 N•m) DO NOT overtighten.
3c. HW-RPM-4R (HWBP-8D and HWAP-8D panels only)
H
Load 1
N
H
Load 2
N
H
Load 3
N
H
Load 4
N
Figure 4 - Dedicated Control Assembly Feed
Input Hot From
Control Breaker
(pre-wired)
Neutral From
Red
Main Lug
(pre-wired)
Black
Torque Terminal Blocks to:
5.3 in-lb to 7.0 in-lb (0.6 N•m to 0.8 N•m)
White
DO NOT overtighten.
Warranty: For warranty information, please see the warranty enclosed with the product, or visit
www.lutron.com/TechnicalDocumentLibrary/warranty.pdf
Lutron and HomeWorks are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the
US and/or other countries.
National Electrical Code and NEC are registered trademarks of the National Fire Protection Association,
Quincy, Massachusetts.
© 2014 - 2019 Lutron Electronics Co., Inc.
Lutron Elec tron ics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299
(continued)
Bypass Jumper
(Do not remove until load
wiring has been tested and
all modules are installed)
Output 1
SH1
H1
N1
Output 2
SH2
H2
Load Neutral 2
N2
Output 3
SH3
H3
Load Neutral 3
N3
Output 4
SH4
H4
Load Neutral 4
N4
Line 1
N
H
Bypass Jumper
(Do not remove until load
wiring has been tested and
all modules are installed)
Red 1
Black 1
Black (CH)
White (CN)
Red 2
Black 2
Red 3
Black 3
Red 4
Black 4
Torque Terminal Blocks to:
5.3 in-lb to 7.0 in-lb (0.6 N•m to 0.8 N•m)
DO NOT overtighten.
Black
Green/Yellow
Red
Black
Gray
Red
Black
Gray
Red
Black
Gray
Red
Black
Gray
HW-RPM-4R
Feed Plug
White
MOVs
(Do Not Remove)

Publicidad

loading

Este manual también es adecuado para:

Hwap-8d-15-120l3Hwbp-8d-15-120l3Hwbp-2s-20-120l3Hwap-8d-20-120l3Hwbp-8d-20-120l3Hwbp-2s-15-120l4 ... Mostrar todo