GB
• Do not connect mixed loads, but only actuators of the same type
per channel group (channels 1..3 or 4..6). Otherwise risk of
overloading.
• In the event of overload, the channels are shut off for at least 6
minutes. Thereafter, the actuator detects the overloaded or short-
circuited channel and switches it off permanently.
• Locate and eliminate the cause of the overload shutoff in strict
observance of the safety warnings.
• To reset the overload shutoff, the actuator must be disconnected
for approximately 5 seconds from the mains supply. After a reset
of an overload shutoff it is no longer possible to detect the
overloaded channel. If the cause of the overload shutoff is not
eliminated, the actuator will shut off again.
Instructions
Instructions
• Connect the servo-drives in frost-sensitive rooms to channels 1
and 4 as these channels are the last that are switched off in the
event of overload.
• Use the output terminals
of 4 servo-drives at maximum.
• Connecting the N-conductor of further devices to the output N-
terminals is not permitted.
Otherwise risk of irreparable damage to the actuator.
• Do not connect capacitive or inductive loads.
Otherwise risk of irreparable damage to the actuator.
• The 'programmed response after bus voltage failure' is available
only after connection of the bus and the mains.
and N exclusively for the connection