Idiomas disponibles

Func.
Code
B022
Overload restriction setting
B023
Deceleration rate at overload restriction
B024
Overload restriction operation mode (2)
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
• 03 Enabled for accel, decel, constant
speed
B025
Overload restriction setting (2)
B026
Deceleration rate at overload restriction (2)
B031
Software lock mode selection
• 00 Low-level access, [SFT] blocks edits
• 01 Low-level access, [SFT] blocks edits
(except F001 and Multi-speed parameters)
• 02 No access to edits
• 03 No access to edits except F001 and
Multi-speed parameters
• 10 High-level access, including B031
B034
Run/power on warning time
B035
Rotational direction restriction
• 00 Enable for both directions
• 01 Enable for forward only
• 02 Enable for reverse only
B036
Reduced voltage start selection
• 00 Short
• 01, 02, 03, 04, 05 (middle)
• 06 Long
B037
Function code display restriction
• 00 Display all
• 01 Display only utilized functions
• 02 Display user-selected functions only
(configure with U01 to U12)
B040
Torque limit selection
• 00 4-quadrant mode
• 01 Selected by 2 input terminals
• 02 From analog O2 input (0 to 200%)
• 03 From expansion card 1
• 04 From expansion card 2
B041
Torque limit (1) (forward-driving in
4-quadrant mode)
B042
Torque limit (2) (reverse-regenerating in
4-quadrant mode)
Name / Description
20
Default Value
–FE / –FU /
–FR
Rated current
x 1.50
1.00
01
Rated current
x 1.50
1.00
01
0.
00
06
00
00
150.
150.
Set
Value

Publicidad