Descargar Imprimir esta página

Wiring The Input Terminals - Lenze EZV Serie Instrucciones Para El Montaje

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Wiring the input terminals

The device can either be connected to single−phase AC systems or to two phase conductors
of three−phase systems (TN, TT or IT system to VDE 0100 T 300/IEC 364−3) with rated
voltages of AC 100 ... 240 V.
{
Danger!
For the operation on two phase conductors of a three−phase system it is vital
to provide an all−pole disconnecting device for the protection of persons.
TN-S
1/N/PE AC 100 ... 240 V
45 ... 65 Hz
L
N
PE
5
L N PE
TN-S
3/N/PE AC 100 ... 240 V
45 ... 65 Hz
L1
L2
L3
N
PE
5
L N PE
5
Circuit−breaker 6 A/ 10 A/ 16 A (characteristic B or C)
EDKZV1200 DE/EN/FR/ES/IT 1.0
TN-C
1/PEN AC 100 ... 240 V
45 ... 65 Hz
L
PEN
5
L N PE
TN-C
3/PEN AC 100 ... 240 V
45 ... 65 Hz
L1
L2
L3
PEN
5
L N PE
l
Electrical installation
Wiring the input terminals
TT
1/N AC 100 ... 240 V
45 ... 65 Hz
L
N
5
L N PE
TT
3/N AC 100 ... 240 V
45 ... 65 Hz
L1
L2
L3
N
5
L N PE
IT
3 AC 100 ... 240 V
45 ... 65 Hz
L1
L2
L3
5
L N PE
ezvxx00−000_06
2
21

Publicidad

loading

Este manual también es adecuado para:

Ezv1200-000Ezv2400-000Ezv4800-000